1.1.1 Operation with ONE charging level
This type of charge is generally used with sealed lead acid batteries that, owing to
the manufacturing technology, have a very narrow voltage range. In fact, the nominal
charging voltage ranges between 2.25÷2.27 V/cell, with a maximum value of 2.3 V/cell.
The picture below shows the charging curves at different charging currents; the
higher is the current, the higher is the restored capacity versus time, the lower is the
recharging time.
Picture 3 – Operation with ONE charging level
1.2
INVERTER
The inverter converts the DC input voltage to AC voltage, stabilized in frequency and
RMS value.
The DC voltage is converted by the IGBT bridge, that uses six switches, controlled
using PWM (Pulse Width Modulation) technology at high commutation frequency. The
PWM generation as well as the control of the operating variables is completely
managed by the microprocessor.
The current transducer CT provides for the monitoring of the input current. Its
feedback signal is managed by the microprocessor to activate the current limitation (see
2.2.3) and the IGBT protection (see 2.2.4).
Picture 4 – Inverter
Содержание B9600FXS
Страница 28: ...OMD39088 rev F 27 Picture 21 Handling of UPS B9600FXS 500 600kVA ...
Страница 39: ...OMD39088 rev F 38 Picture 28 Terminal board B9600FXS 400kVA side view ...
Страница 40: ...OMD39088 rev F 39 Picture 29 Terminal board B9600FXS 500 600 800kVA front view ...
Страница 41: ...OMD39088 rev F 40 Picture 30 Terminal board B9600FXS 500 600 800kVA side view ...
Страница 63: ...OMD39088 rev F 62 Picture 50 Example of UPS units in Sync Load configuration single configuration ...
Страница 65: ...OMD39088 rev F 64 Picture 52 Example of UPS units in Sync Load configuration parallel configuration ...