OMD10078 rev F
34
UPS (kVA)
60 80 100
125
160
X – mm
270
260
Y – mm
18
30
Z – mm
598
615
Connection data of terminal boards
UPS (kVA)
60 80 100 125 160
Section (mm
2
)
35 35 70
25x6
30x5
Hole diameter (mm)
11 11 11 11 11
Cable terminal hole
M6
M6 M8 M10
M10
Max. cable section (mm
2
)
35 35 70
2x95
2x150
Tightening force (Nm)
5 5 10
15
20
4.8
CONNECTION OF POWER CABLES
For the electric connection of UPS B9000FXS, connect the following cables:
DC supply from the battery;
AC supply from the rectifier and bypass supply mains;
AC output to the loads.
Injury hazard due to electric shock!
Very high voltages are present at the ends of the cables coming from the
battery:
isolate the battery via DC circuit breakers before connecting it to the
UPS;
connect the ground cable to the relevant bar before carrying out any
other connection inside the device.
Risk of damages to the device due to insufficient insulation
The cables must be protected from short-circuits and leakage currents to
earth;
the connection points must be hermetically sealed to prevent the air from
being sucked through the cable passage.
Risk of damages to the device due to incorrect wiring
To connect the device, follow the electrical drawing scrupulously and respect
the polarity of cables.