OMD10078 rev F
27
4.4.3 Minimum distances from the walls and ventilation
The UPS must be so installed as to ensure its serviceability and to allow a correct air
flow as much as possible.
With regard to the minimum distances from the walls, for all of the UPS sizes the
same installation conditions apply as indicated in the table below.
Picture 23 – Minimum distances from the walls
A (mm) B (mm)
C (mm)
D (mm)
1000 700 200 50
The table below shows the air volume required for an optimal ventilation and cooling
of the UPS.
A (mm) B (mm)
C (mm)
D (mm)
1000 700 200 300
UPS (kVA)
60
80
100
125
160
Air volume (m
3
/h) 1600
1800
2100 2300 2500