66
Wiring section from the regulator to the battery:
Table for Copper cables (Cu).
Model
Batería (V) 0-5m
(mm
2
)
0-5m
(AWG)
5m-10m
(mm
2
)
5m-10m
(AWG)
Bornay 13+
12
50
1/0
95
4/0
Bornay 13+
24
35
2
70
2/0
Bornay 13+
48
25
3
50
1/0
Bornay 25.2+ *
12
50
1/0
120
5/0
Bornay 25.2+
24
50
1/0
95
4/0
Bornay 25.2+
48
35
2
70
2/0
Bornay 25.3+ *
12
50
1/0
120
5/0
Bornay 25.3+ **
24
50
1/0
95
4/0
Bornay 25.3+
48
50
1/0
95
4/0
Cables longer than 10m are not recommended for the connection between
the regulator and the batteries. If, for some reason, it is required to install
longer cables, it must be approved by Bornay.
Bornay Aerogeneradores SLU
P.I. Riu, Cno. del Riu, s/n
Tel. +34/965560025 [email protected]
0320 Castalla (Alicante) España
Fax +34/965560752
EN
G
Содержание WIND+
Страница 1: ...Regulador de carga MPPT MPPT Charge controller Manual Versión 2 0 01 19 ENG ESP ...
Страница 16: ...16 Temperatura del interior del regulador Velocidad de viento medida por el anemómetro ESP ...
Страница 18: ...18 ESP ...
Страница 31: ...31 Detalle de las dimensiones del equipo Dimensiones del embalaje ESP ...
Страница 34: ...34 MPPT Charge Controller Manual Installation Operation Maintenance ENG ...
Страница 51: ...51 BATTERY VOLTAGE V BATTERY STRENGTH A ENG ...
Страница 54: ...54 Screen to select windturbine model MODEL OF THE WIND TURBINE ENG ...
Страница 63: ...63 Mounting in the wall Below are shown the distances of the holes for mounting the unit on the wall ENG ...
Страница 64: ...64 Detail of the dimensions of the regulator Dimensions of the Packaging ENG ...