16
3) BROWN (L2) : Set the cam position to “5.0” which is indicated on the cam shaft by manual
(2nd. middle fire opening angle position adjusting).
4) BLUE (L1): Set the cam position to “5.3” which is indicated on the cam shaft by manual
( Position adjusting when returning from 3rd. high fire to 2nd. middle fire).
5) YELLOW (L5) : Set the cam position to “6.0”which is indicated on the cam shaft by manual
(Position adjusting for 3rd. solenoid valve opening movement).
6) RED (L6) : Set the cam position to “8.0” which is indicated on the cam shaft by manual
(3rd. high fire opening angle position adjusting cam).
Note:
Angle adjusting of the damper blade affects to the combustion condition and efficiency significantly and causes for
smoke. Do not adjust it at his discretion. Wrong direction is caused for smoke.
(8) Adjusting Method for the Water Level Device (BWC-3000L)
1) Direction for use
Water Level Control Conversion Switch
This is a control device which has functions of water control,
concentration blowing-off and accumulation of combustion time.
[1] Combustion Time Check Conversion Mode
When pushing the conversion switch on the left side of the
water level unit, the LED lamp of the high fire, medium fire
and low fire are changed in sequence and the accumulated
combustion time is indicated on the monitor.
Ex) In case that the following indication are shown on the
monitor when pushing the conversion switch:
a) When the high fire[PH] lamp is lit up and [1][3] indication
is shown up on the monitor, total high fire operation time is
13 hours.
b) When the medium fire[PM] and the low fire[PL], the
indication is shown in the same method as the above.
[2] Water Level Control Conversion Switch
(BWC – 3000L)
This is a switch which has functions of 3 position water level control and 5 position water level
control located on the upper position of the left side, and the function is being able to converted each other.
[3] Three position control(0.5 - 1.5 T/H) - E1, E2, E3 water level detection
(E1 : High water level, E2 : Medium water level, E3 : Low water level).
[4] Five position control(2.0 - 3.0 T/H) - E1, E2, E3, E4, E5 water level detection
(E1 : High water level, E2 : Medium water level, E3 : Low water level, E4 : Forced water level,
E5 : Safe water level).
When each water level detection lamp is lit up, current water level is indicated.