Check the voltage at the input of the reactor (transformer side). If the voltage stays
above 90% of the nominal voltage, you can operate your system without the
reactor. If the voltage drops below 90% of the nominal voltage, you may need to
upsize your input transformer or get a transformer with lower impedance for proper
operation.