Operating manual for PROFINET fieldbus | DOC01725815-0003 | 2016-12 | V2.04 EN
19
DANGER!
Risk of death due to electrical shock!
Death or serious injury!
De-energize drive controller and secure it against being restarted.
3. Installation
3.1 Configuration of the drive controller for PROFINET
In order that the drive controller can be controlled by the fieldbus, the following basic parameters
must be set using the Vplus Dec tool, MMI or PROFINET master:
Set parameter 1.130 (target value source) to fieldbus "9"
Set parameter 1.131 (target value approval) to fieldbus "6"
There is also the possibility of configuring the basic parameters using the master via the
PROFINET. However, this can only be done once the communication has been installed.
The user must choose the set of parameters appropriate to him.
3.2 DGM bus address
In order that an DGM, equipped with a PROFINET communication card, can be clearly
recognized in a PROFINET system, it must be assigned an IP address.
The IP address can be assigned automatically or manually.
Select the corresponding option in the master.
Parameters 6.067 (IP number), 6.068 (netmask) and 6.069 (gateway) can be set to suit the
network environment.
If parameters are not set, the following default
values apply:
IP:
192.168.0.31
Netmask:
255.255.255.0
Gateway:
0.0.0.0
3.3 Installing the DGM GSDML file
A "device-specific information file" is required to use the DGM drive controller with PROFINET.
Download the "PROFINET fieldbus for DGM" ZIP file from the download area on our website under
the following link:
Embed the GSDML file as required by the PROFINET master you are using.