12/16
Operating Instructions ACU
93
Display
Description
dSt. 4
The data are copied to data set 4 of the frequency inverter.
dSt. F1
The data are copied to file 1 of the control unit.
1)
dSt. F2
The data are copied to file 2 of the control unit.
1)
dSt. F3
The data are copied to file 3 of the control unit.
1)
dSt. F4
The data are copied to file 4 of the control unit.
1)
dSt. F5
The data are copied to file 5 of the control unit.
1)
dSt. F6
The data are copied to file 6 of the control unit.
1)
dSt. F7
The data are copied to file 7 of the control unit.
1)
dSt. F8
The data are copied to file 8 of the control unit.
1)
1)
Already existing files will not be offered as copy target.
8.5.5
Copy Operation
Before the parameter settings are transferred to the frequency inverter, the individual
parameter values are checked.
The value range and the parameter settings can differ according to the power range of
the frequency inverter. Parameter values which are outside of the value range will
trigger a copy error message. In case a device error is triggered as a result of copying,
the device error will only be displayed once the copying has been completed.
While the copy operation is in process, the message
COPY
and, as a
progress indicator, the number of the currently copied parameter will be
displayed
In the case of the Act function, the active parameter values are copied only.
Using the ALL function, parameters which are not relevant to the selected
configuration are copied, too.
Depending on the configuration selected (ALL or Act), the copy operation will
be completed after approx. 100 seconds and the message
rdY
will be
displayed.
Press the ENT key to switch to the copy menu. Use the ESC key to switch to
the target selection menu.
If the ESC key is pressed during the copy operation, the copy operation is
aborted before the transmission of the data is complete. The message
Abr
and the number of the last parameter which was copied are displayed.
Press the ENT key to return to the selection in the copy menu. Use the ESC
key to switch to the target selection menu.
8.5.6
Error messages
The copy function archives all parameters, regardless of the access control
and the value range. Some of the parameters are only writable if the
frequency inverter is not in operation. The controller enable input (S1IND,
S7IND) may not be activated during the copy operation, otherwise the data
transmission is aborted. The message
StO
and the number of the last
parameter which was copied are displayed. If the controller enable input is
deactivated again, the aborted copy operation is continued.
The data transmission from the selected source to the destination is
continuously monitored by the copy function. If an error occurs, the copy
operation is aborted and the message
Err
and an error code are displayed.