5

 

Figure 1. Connection Diagram. 

Table 7. How to Connect an Actuator to the S2000-SP4/220 

Manufacturer 

Article 

How to Connect 

Belimo 

BLF-230 

Directly to the required output, the unused output is shunted 

by a 47 kOhm @ 2 W resistance 

Belimo 

BE-230 

Directly, without additional elements 

Belimo 

BLE-230 

Directly, without additional elements 

 

Содержание S2000-SP4/220

Страница 1: ...ended ceiling or on another constructions near the connected executive device protected against atmospheric fallouts mechanical damage and unauthorized access The module is designed for round the clock operation 1 1 6 The module must not be used in aggressive medium or dust condition or in explosion hazardous premises 1 1 Specifications Table 1 Specifications 1 Input Voltage Communication Part 8 V...

Страница 2: ...the output relative to the N terminal of the power input Table 3 States of an Output Circuit Condition Output State L R Terminal N R Terminal Norm On Input Voltage Value 0 3 V to 0 9 V Off 0 35 V to 4 5 V 0 3 V to 0 6 V Open Failure On Input Voltage Value 0 V to 0 3 V Off 4 5 V to 5 V 0 V to 0 3 V Short Failure On Input Voltage Value Input Voltage Value Off 0 3 V to 0 6 V 0 3 V to 0 6 V Note If an...

Страница 3: ...rent position of the damper s blades open closed 2 2 3 A limit switch circuit can be in one of the four states which are defined by the circuit resistance Table 5 shows the ranges of resistance values for relative states of the limit switch circuits 2 3 TEST Button 2 3 1 The module provides connecting an external button TEST 2 3 2 The TEST button is designed to test damper operation conditions man...

Страница 4: ...le MUST be performed by qualified engineers 3 2 Preparation for Using 3 2 1 If necessary change the module s addresses within the polling loop of the connected S2000 KDL The addresses of the module must not be the same as addresses of any devices connected to the same polling loop 3 2 2 If you are going to use the module with a single power supply the power supply should be connected to both power...

Страница 5: ...r to the S2000 SP4 220 Manufacturer Article How to Connect Belimo BLF 230 Directly to the required output the unused output is shunted by a 47 kOhm 2 W resistance Belimo BE 230 Directly without additional elements Belimo BLE 230 Directly without additional elements ...

Страница 6: ...Address command from the console or PC specifying the old address the first of the five old addresses and the new address the first of the five new addresses of the module In such case the console or PC will display events about disconnecting the devices with the old addresses and finding the devices with the newly given addresses 3 4 Using The module operates under the connected S2000 KDL control...

Страница 7: ...vert the current damper state For example if the damper is in the operating state pushing the TEST button will run the mechanism of switching the damper to the safety state 4 MAINTENANCE Please inspect the module annually by doing the following 1 Check the S2000 SP4 220 visually for contaminations and mechanical damage 2 Test the S2000 SP4 220 operability as said above 3 Verify the S2000 SP4 220 f...

Отзывы: