background image

 

Table 1 

LED 

Performance 

Condition 

Description 

Text on the IPDL-

152 Tester 

Display 

Flashes with 
red once per 

four seconds 

Norm 

The received signal meets norm 
conditions 

Норма

” / “Norm” 

Lit steady with 

red 

 

Waiting for establishing 
communications with the PL 
controller 

 

Test 

The TEST button has been 
pressed 

 

Fire 

The received signal value has 
dropped down to the alarm 
threshold 

Пожар

” / “Fire” 

Flashes four 

times with red 

every four 

seconds 

 

Programming the detector with an 
address 

 

Blinking with 
red with blue 

flashes 

 

Fire in Progress 
The received signal value has 
dropped down to the alarm 
threshold but the Fire status has 
not yet been stated 

Набор

 

Пож

.” / 

“Fire in Progress” 

--//-- 

with rare 

amber flashes 

 

Operation Mode Changed 
Positions of the DIP switches were 
changed after exiting the alignment 
mode 

Норма

” / “Norm” 

with “Switched” 

from time to time 

--//-- 

with green 

flashes 

 

Establishing of the Test status after 
pressing the relevant button 

 

--//-- 

with amber 

flashes 

 

Establishing of the Trouble status 
after pressing the relevant button 

 

--//-- 

with white 

flashes 

 

Trouble in Progress 
Conditions for some Trouble status 
have occurred but this status has 
not yet been established 

Набор

 

Неис

.” / 

“Trouble in 

Progress” 

Flashes with 

red twice per 

second 

Trouble 

The TROUBLE button has been 
pressed 

 

Trouble-Beam  
The received signal has dropped 
by more than 80% 

Н

луч

” / “TR 

Beam” 

Trouble-Out-of-Range 
The values written into the 
EEPROM are out of the 
permissible range 

Н

допуска

” / 

“TR Out-of-Range” 

Trouble-Memory 
Main data and backup data stored 
in the EEPROM are not the same 

Н

память

.” / 

“TR Memory” 

Trouble-High 
The compensated signal has 
reached the upper threshold 

Н

превыш

.” / 

“TR High” 

Trouble-Low 
The compensated signal has 
dropped down to lower threshold 

Н

снижен

.” / 

“TR Low” 

Содержание S2000-IPDL

Страница 1: ... necessary to comply with safety measures in accordance with Regulations for Operation of Consumers Electrical Installations and Safety Rules for Operation of Consumers Electrical Installations While installing and maintaining the detector please comply with the rules for working at heights 2 MOUNTING 2 1 The units of the detector should be attached to the building structures generally with the he...

Страница 2: ...he detector enable connecting wires with cross section area 0 2 to 1 5 sq mm wire diameter 0 5 to 1 3 mm If wires of 0 8 mm diameter or less are used then their ends shall be looped 2 8 The housing of the transceiver unit can be removed if only there are no locking screws in the latches at the top and the bottom of the housing To remove the housing release both the latches pressing on them and pul...

Страница 3: ...0 m Range 30 to 120 m 25 to 100 m 20 to 80 m S2000 IPDL Transceiver Mounting Kit 5 to 120 m Reflector Four elements max Mounting Kit Rotated by 90 Remote Indicator and Control Unit Rotated by 90 S Type Reflector XS Type Reflector 1 Dimensions for information 2 The distance between Transceiver Unit and Remote Indicator and Control Unit should not exceed 30 m ...

Страница 4: ... at least 5 second until the red indicator illuminates The panel PC shall display the events of loss of communication with the device assigned with an old address and finding a device with the new address If several devices were assigned with equal addresses set then there will be no messages about loss of communications for old addresses 4 3 If however it is necessary to change the detector addre...

Страница 5: ... second one If you failed to alter this performance then with great probability the detector is improper 5 1 6 If the detector exits the alignment mode normally it shall enter in the Norm state indicating this by red flashing once per four seconds 5 1 7 Arm the detector 5 1 8 Press the TROUBLE button on the detector s board and observe fast flashing with amber Trouble in Progress followed by flash...

Страница 6: ... after exiting the alignment mode Норма Norm with Switched from time to time with green flashes Establishing of the Test status after pressing the relevant button with amber flashes Establishing of the Trouble status after pressing the relevant button with white flashes Trouble in Progress Conditions for some Trouble status have occurred but this status has not yet been established Набор Неис Trou...

Страница 7: ...obscuration for the reflecting surface and moreover L Type reflectors are equipped with an additional scale at their lower edges which is to be used when the reflectors are arranged with two ones in a row 4 2 2 2 Since the S2000 IPDL is a single ended detector and optical beam crosses the monitored area twice then for simulating the beam degradation by a required value the percentage of obscuratio...

Страница 8: ...nt buttons incorporated in remote control unit and duplicated in the detector 4 2 3 2 The relevant button TEST or TROUBLE shall be pressed and held pressed at least for five seconds 6 GETTING STARTED In order the detector to operate under a polling loop controller in an Orion ISS it should be assigned to a polling loop address and relevant settings should be carried out see User s Manual ...

Отзывы: