reflector, for example to put the transceiver on a table with the lens facing up using the ceiling 
as a reflector. 

5.1.3  For  testing  operability,  power  up  the  control  panel  or  PC  and  the  polling  loop  controller 
with the detector connected to the last one. 

5.1.4  Activate  the  alignment  mode  by  sliding  the  DIP  switch  “1”  to  the  ON  position.  Visually 
inspect  fast  pulsing  (faster  than  five  flashes  per  second)  in  red  (which  means  selecting  an 
optimal gain with rewriting the maximum achieved level of received signal) followed by pulsing 
most of the time in blue (Very Close) with normal frequency (approximately twice per second). 
In particular, there can be rare flashes with amber (Less) or red (More). Having achieved such 
condition, you can terminate the alignment by sliding the DIP switch “1” to the OFF position and 
waiting  for  approximately  one  minute  until  the  detector  automatically  quits  this  mode  having 
rewritten new values of installation parameters into the non-volatile memory. 

 

After detector’s having entered to the alignment mode the control panel or PC shall 
receive a Test of Fire Alarm event depending on the current settings 

5.1.5  If the alignment mode has established but the LED rapidly flashes with white (Too Low) or 
blue  (Two  High)  then  take  measures  to  increase  the  reflected  signal  in  the  first  case  or  to 
reduce the reflected signal in the second one. If you failed to alter this performance then with 
great probability the detector is improper. 

5.1.6  If the detector exits the alignment mode normally it shall enter in the Norm state indicating 
this by red flashing once per four seconds. 

5.1.7  Arm the detector. 

5.1.8  Press the TROUBLE button on the detector’s board and observe fast flashing with amber 
(“Trouble  in  Progress”)  followed  by  flashing  in  red  with  the  trouble  pattern.  After  releasing  the 
button the detector will enter normal state in some time. 

5.1.9  Press  the  TEST  button  on  the  detector’s  board  and  observe  fast  green  pulsing  at  first 
(“Test  in  Progress”)  followed  by  solid  illuminating  with  red.  The  full-range  verification  of  the 
operability of the detector is completed now. If any problems were detected during verification 
the  detector  should  be  sent  to  the  manufacturer  for  repair,  however,  it  is  recommended  to 
contact  preliminary  the  technical  support  service  in  order  to  verify  the  validity  of  the  checks 
performed. 

5.2  Testing Performance of the Detectors 

5.2.1 General Guidelines for Testing 

5.2.1.1.  Performance  of  visual  indication  when  the  detector  displays  its  conditions  in  the 
operation mode and in the alignment mode is crucially different. Table 1 contains descriptions 
of  various  conditions  of  the  detector  for  the  operation  mode,  their  textual  names,  and  the 
ways  to  display  these  conditions  by  means  of  detector’s  indication  and  on  the  LCD  of  an 
IPDL-152 test station. 

5.2.1.2.  Prior  to  testing  the  detector  please  read  and  understand  the  information  from 
Table 1. 

 

Содержание S2000-IPDL

Страница 1: ... necessary to comply with safety measures in accordance with Regulations for Operation of Consumers Electrical Installations and Safety Rules for Operation of Consumers Electrical Installations While installing and maintaining the detector please comply with the rules for working at heights 2 MOUNTING 2 1 The units of the detector should be attached to the building structures generally with the he...

Страница 2: ...he detector enable connecting wires with cross section area 0 2 to 1 5 sq mm wire diameter 0 5 to 1 3 mm If wires of 0 8 mm diameter or less are used then their ends shall be looped 2 8 The housing of the transceiver unit can be removed if only there are no locking screws in the latches at the top and the bottom of the housing To remove the housing release both the latches pressing on them and pul...

Страница 3: ...0 m Range 30 to 120 m 25 to 100 m 20 to 80 m S2000 IPDL Transceiver Mounting Kit 5 to 120 m Reflector Four elements max Mounting Kit Rotated by 90 Remote Indicator and Control Unit Rotated by 90 S Type Reflector XS Type Reflector 1 Dimensions for information 2 The distance between Transceiver Unit and Remote Indicator and Control Unit should not exceed 30 m ...

Страница 4: ... at least 5 second until the red indicator illuminates The panel PC shall display the events of loss of communication with the device assigned with an old address and finding a device with the new address If several devices were assigned with equal addresses set then there will be no messages about loss of communications for old addresses 4 3 If however it is necessary to change the detector addre...

Страница 5: ... second one If you failed to alter this performance then with great probability the detector is improper 5 1 6 If the detector exits the alignment mode normally it shall enter in the Norm state indicating this by red flashing once per four seconds 5 1 7 Arm the detector 5 1 8 Press the TROUBLE button on the detector s board and observe fast flashing with amber Trouble in Progress followed by flash...

Страница 6: ... after exiting the alignment mode Норма Norm with Switched from time to time with green flashes Establishing of the Test status after pressing the relevant button with amber flashes Establishing of the Trouble status after pressing the relevant button with white flashes Trouble in Progress Conditions for some Trouble status have occurred but this status has not yet been established Набор Неис Trou...

Страница 7: ...obscuration for the reflecting surface and moreover L Type reflectors are equipped with an additional scale at their lower edges which is to be used when the reflectors are arranged with two ones in a row 4 2 2 2 Since the S2000 IPDL is a single ended detector and optical beam crosses the monitored area twice then for simulating the beam degradation by a required value the percentage of obscuratio...

Страница 8: ...nt buttons incorporated in remote control unit and duplicated in the detector 4 2 3 2 The relevant button TEST or TROUBLE shall be pressed and held pressed at least for five seconds 6 GETTING STARTED In order the detector to operate under a polling loop controller in an Orion ISS it should be assigned to a polling loop address and relevant settings should be carried out see User s Manual ...

Отзывы: