background image

 

8

The indication type “Trouble” is meant for indication of troubles only. It can be used both for 

security and for fire partitions (zones). 

Table 7.

 Performance of LEDs “1” – “60” for Indication Type “

Trouble

 

Partition Status 

Indicator “1” – “60” Performance 

Trouble 

Pulses with amber: 0.25 s On / 1.75 s Off 

Disarmed 

Lit steady in amber 

Disabled 

Lit steady in amber 

The indication type “Operated Appliance” is designed to indicate conditions of dampers, pumps, 

and other appliances. The integrated indicators “Start”, “Abort (Stop)”, “Trouble”, and “Disabled” 
of the modular fire alarm control and indicating device are located on the relevant S2000M. 

Table 8.

 Performance of LEDs “1” – “60” for Indication Type “

Operated Appliance

 

Partition Status 

Indicator “1” – “60” Performance 

Output Activated 

Lit steady in red 

Start Delay when there are less than 5 s left 

Pulses with red four times per second 

Start Delay when there are less than 15 s left 

Pulses with red twice per second 

Start Delay when there are more than 15 s left 

Pulses with red once per second 

Start Delay Hold 

Pulses with amber by the same way as for start delay 

Output Activation Failed, Trouble 

Pulses with amber: 0.25 s On / 1.75 s Off 

Disarmed 

Lit steady in amber 

Operating Position, Pump On 

Lit steady in red 

Output Abort/Stop 

Lit steady in amber 

Initial Position, Pump Off 

Lit steady in green 

Disabled

 

Lit steady in amber 

Note: The Operated Appliance indication mode is supported only by S2000M control panels of 

versions 2.07+. 

The  indication  types  “Auxiliary”,  “Auxiliary 2”,  and  “Auxiliary 3”  are  expected  for  signaling 

about  conditions  of  various  engineering  equipment,  doors,  etc.  which  are  monitored  by  means  of 
auxiliary alarm loops. The types Auxiliary and Auxiliary 2 imply that the relevant partition contains 
only auxiliary alarm loop, and various troubles of this loop are indicated with the highest priority. 
These two tactics differ by the way to indicate activation of the auxiliary alarm loop (for Auxiliary 
the LED illuminates steady with red while for Auxiliary 2 the LED pulses with amber). For the type 
Auxiliary 3  indication  of  troubles  in  a  partition  is  of  less  priority  relative  to  auxiliary  alarm  loop 
activation and restoring. This provides indicating only conditions of the auxiliary alarm loop even if 
the partition integrates also alarm loops of other types. If only the auxiliary alarm loop is included 
into a partition then indication types Auxiliary and Auxiliary 3 operate near to identically. 

Table 9.

 Performance of LEDs “1” – “60” for Indication Type “

Auxiliary

 

Partition Status 

Indicator “1” – “60” Performance 

Trouble, Tamper Alarm 

Pulses with amber: 0.25 s On / 1.75 s Off 

Disarmed 

Lit steady in amber  

Auxiliary Input Activated 

Lit steady in red  

Auxiliary Input Restored 

Lit steady in green 

Disabled 

Lit steady in amber 

Table 10.

 Performance of LEDs “1” – “60” for Indication Type “

Auxiliary 2

 

Partition Status 

Indicator “1” – “60” Performance 

Trouble 

Pulses with amber: 0.25 s On / 1.75 s Off 

Disarmed 

Lit steady in amber 

Auxiliary Input Activated 

Pulses with amber: 0.5 s On / 0.5 s Off 

Содержание S2000-BI Rev.02

Страница 1: ... to be operated in aggressive and dusty environments and in ex hazardous premises 1 2 Specifications Light Indication 60 two color LEDs to indicate conditions of up to 60 partitions of Orion ISS 8 single color LEDs to display alarms and troubles in Orion ISS One LED to indicate the module conditions One LED to show that a sound is silenced One LED to show whether or not operating by iButton is per...

Страница 2: ...2 S2000 BI S2000 BI Rev 02 Figure 1 View and Overall and Mounting Dimensions of the Module ...

Страница 3: ... fix the module on the wall Figure 2 Opening Cover Panel 2 2 Wiring the Module 2 2 1 Connect wires to the terminals as shown in Figure 3 2 2 2 Please observe polarity while connecting the module to the power supply 2 2 3 The cross section of wires should not exceed 1 5 sq mm 2 2 4 If the module the control panel or other Orion system devices connected to the RS 485 interface bus are supplied with ...

Страница 4: ...e 4 shows the display of the S2000M panel with the relevant message 3 5 8 If several messages accumulated by the module have been received by the panel you can browse them by the arrow buttons and on the S2000M 3 6 Testing Indication in Self Diagnostic Mode Indication Test 3 6 1 Initiate the self diagnostic mode by starting the indication test from the network controller 3 6 2 The module s indicat...

Страница 5: ...ring Access Control Security Alarm 3 Sound Alarms for Fire 2 Fire Prealarm Sound alarms can be disabled if the S2000M network controller is located near the module Disabled or On for indefinite time On 4 Sound Alarm Duration for Trouble Condition The time on elapsing which a sound alarm will be silenced automatically Sound alarms can be disabled if the S2000M network controller is located near the...

Страница 6: ...op troubles troubles of outputs power failures communication loss etc Fault Input Open Failure Input Short Failure Configuration Error Tamper Alarm Output Open Failure Output Short Failure Mains Failed Overload Battery Test Error Power Failed Charger Failed Battery Failed Low Battery Low Backup Battery Level Above Limit Level Below Limit Noise Actuator Failure Actuator Error Service Required Tempe...

Страница 7: ...n amber with S2000M of version 3 00 Note The indication type Security 3 Alarm operates correctly only if the control panel S2000M of version 2 03 or higher is in use The indication type Fire Alarm is meant to indicate conditions of individual fire partitions zones The integrated indicators Fire Trouble and Disabled of the modular fire alarm control and indicating equipment are located of the S2000...

Страница 8: ...ed only by S2000M control panels of versions 2 07 The indication types Auxiliary Auxiliary 2 and Auxiliary 3 are expected for signaling about conditions of various engineering equipment doors etc which are monitored by means of auxiliary alarm loops The types Auxiliary and Auxiliary 2 imply that the relevant partition contains only auxiliary alarm loop and various troubles of this loop are indicat...

Страница 9: ...h red 0 5 s On 0 5 s Off Normal Temperature Normal Level Lit steady in green Disabled Lit steady in amber The indication type Leakage Monitoring is used to warn about flooding Table 13 Performance of LEDs 1 60 for Indication Type Leakage Monitoring Partition Status Indicator 1 60 Performance Flooding Alarm Pulses with red 0 5 s On 0 5 s Off Trouble Pulses with amber 0 25 s On 1 75 s Off Flood Dete...

Страница 10: ...ious conditions then these indicators provide fast estimation of current situation and defining action priority Table 16 describes performance of the indicators after alarms have been received Table 16 Performance of Single Color LEDs Partition Status LED Performance Fire 2 Alarm FIRE 2 Red Fire Alarm FIRE Red 0 25 s On 0 25 s Off Prealarm PREALARM Red 0 25 s On 1 75 s Off Intrusion Alarm Flood Al...

Страница 11: ...0 8 s On 0 2 s Off Fire Alarm 0 6 s On 0 4 s Off Fire Prealarm 0 25 s twice 1 25 s Off Intrusion Alarm 0 25 s On 0 25 s Off Panic Alarm Panic Alarm Duress 0 25 s On 0 25 s Off Trouble 0 25 s On 1 75 s Off Access Request touching with an iButton Turns on for 0 25 s Access Denied Turns on for 1 s Access Granted Turns on for 0 25 s Others Off Table 19 Indication Mode Compatibility Indication Type Sup...

Страница 12: ...ts are sent with time stamps determined by internal clock of the module All LEDs except for the power indicator turn off while the TROUBLE LED turns on Once per hour the module automatically synchronizes with the S2000M control panel 5 5 2 The module provides buffering event transmitted over RS 485 5 6 Network Address Network Address is meant to identify the module uniquely within an Orion integra...

Страница 13: ...nstructions for transportation storage installation and usage 8 2 The average lifetime of the module is at least 10 years 8 3 Warranty period is 18 months since putting the module into operation but no more than 24 months from the manufacturer s date of issue 8 4 While submitting the module for repair please apply a report describing the failure 8 5 If you have any problems with programming or ope...

Страница 14: ...rtificate РОСС RU ИК32 К00153 10 ACCEPTANCE AND PACKAGING CERTIFICATE Indicator Module S2000 BI S2000 BI Rev 02 Serial Number___________________ Is manufactured accepted in accordance with mandatory requirements of state standards and actual technical documentation packaged by CJSC NVP Bolid and approved as proper for operation Responsible for acceptance and packaging QCD _________________________...

Отзывы: