The indication type “Trouble” is meant for indication of troubles only. It can be used both for
security and for fire partitions (zones).
Table 7.
Performance of LEDs “1” – “60” for Indication Type “
Trouble
”
Partition Status
Indicator “1” – “60” Performance
Trouble
Pulses with amber: 0.25 s On / 1.75 s Off
Disarmed
Lit steady in amber
Disabled
Lit steady in amber
The indication type “Operated Appliance” is designed to indicate conditions of dampers, pumps,
and other appliances. The integrated indicators “Start”, “Abort (Stop)”, “Trouble”, and “Disabled”
of the modular fire alarm control and indicating device are located on the relevant S2000M.
Table 8.
Performance of LEDs “1” – “60” for Indication Type “
Operated Appliance
”
Partition Status
Indicator “1” – “60” Performance
Output Activated
Lit steady in red
Start Delay when there are less than 5 s left
Pulses with red four times per second
Start Delay when there are less than 15 s left
Pulses with red twice per second
Start Delay when there are more than 15 s left
Pulses with red once per second
Start Delay Hold
Pulses with amber by the same way as for start delay
Output Activation Failed, Trouble
Pulses with amber: 0.25 s On / 1.75 s Off
Disarmed
Lit steady in amber
Operating Position, Pump On
Lit steady in red
Output Abort/Stop
Lit steady in amber
Initial Position, Pump Off
Lit steady in green
Disabled
Lit steady in amber
Note: The Operated Appliance indication mode is supported only by S2000M control panels of
versions 2.07+.
The indication types “Auxiliary”, “Auxiliary 2”, and “Auxiliary 3” are expected for signaling
about conditions of various engineering equipment, doors, etc. which are monitored by means of
auxiliary alarm loops. The types Auxiliary and Auxiliary 2 imply that the relevant partition contains
only auxiliary alarm loop, and various troubles of this loop are indicated with the highest priority.
These two tactics differ by the way to indicate activation of the auxiliary alarm loop (for Auxiliary
the LED illuminates steady with red while for Auxiliary 2 the LED pulses with amber). For the type
Auxiliary 3 indication of troubles in a partition is of less priority relative to auxiliary alarm loop
activation and restoring. This provides indicating only conditions of the auxiliary alarm loop even if
the partition integrates also alarm loops of other types. If only the auxiliary alarm loop is included
into a partition then indication types Auxiliary and Auxiliary 3 operate near to identically.
Table 9.
Performance of LEDs “1” – “60” for Indication Type “
Auxiliary
”
Partition Status
Indicator “1” – “60” Performance
Trouble, Tamper Alarm
Pulses with amber: 0.25 s On / 1.75 s Off
Disarmed
Lit steady in amber
Auxiliary Input Activated
Lit steady in red
Auxiliary Input Restored
Lit steady in green
Disabled
Lit steady in amber
Table 10.
Performance of LEDs “1” – “60” for Indication Type “
Auxiliary 2
”
Partition Status
Indicator “1” – “60” Performance
Trouble
Pulses with amber: 0.25 s On / 1.75 s Off
Disarmed
Lit steady in amber
Auxiliary Input Activated
Pulses with amber: 0.5 s On / 0.5 s Off