RATIO.pm6.5 - USA
Page 1.12
RATIO
BOGE – RATIO compressor control for screw compressors
Control Parameterization
1.5
Error key table
Each message is automatically
registered by the control, to-
gether with the associated time,
thus putting an overview at the
disposal of BOGE-Service.
1
) adjustable
Error Meaning
Compr.-
No.
cut-out
0
Compr. air treatment (dryer or condensate drain gives error message)
1
)
1
Final compression temperature > 110°C, 230°F
X
2
Motor temperature too high
X
3
Excessive current of vent. motor
X
4
Incorrect direction of rotation
X
5
Excessive compressor system pressure
X
6
Excessive diff. pressure of intake filter
7
Excessive diff. pressure of oil filter
8
Excessive diff. pressure of oil separator
9
No output
X
10
Motor servicing due
11
Compressor servicing due
12
System pressure decrease too slow
13
Frequency converter gives error message
X
14
Temperature too low
X
15
Suction control faulty (suction control or solenoid valve, if necessary clean
proportional controller)
16
Network pressure transmitter faulty
X
System pressure increases too quickly (lack of oil, oil too old or even with
17
monitoring of the rotational direction a false rotational direction cannot be
X
excluded)
18
Master control tries to go below P
min
– cf parameterization "External output enable"
Previous net switch-on phase was too short (possible reasons: coil short-circuit
19
'solenoid valve', 'delta contactor' or 'ventilator contactor')
→
automatically
increased delay time in corr. with permissible number of motor switch cycles
20
Master control tires to exceed P
max
– cf parameterization "External output enable"
21
Receiver or wearing parts inspection due
22
Not assigned here
23
Not assigned here
24
Not assigned here
25
Control unit Reconciliation error
X
26
Control unit O-key does not open
X
27
Control unit I-key does not open
X
28
Control unit
i
-key does not open
29
Control unit
↵
-key does not open
30
Control unit "arrow up" does not open
31
Control unit "arrow down" does not open
32
Network pressure-transmitter wire breakage
X
33
Compr.system pressure-transmitter wire breakage
X
34
Compr.system pressure-transmitter faulty
X
35
Excessive diff. pressure return valve
36
Bus Life-Bit did not toggle
38
Current of compressor motor is too high
X
Содержание RATIO
Страница 3: ...Page II BOGE RATIO compressor control for screw compressors Inhalt pm6 5 USA Index ...
Страница 5: ...Page IV BOGE RATIO compressor control for screw compressors Inhalt pm6 5 USA Index ...
Страница 31: ...RATIO pm6 5 USA Page 1 26 RATIO BOGE RATIO compressor control for screw compressors ...