WIRING DESCRIPTIONS
BLACK
NOTES
WHITE/BLACK
NORMAL HOT
DESCRIPTION
WIRE COLOR
WALL SWITCH INPUT (SELF-TEST INPUT)
MUST BE FROM SAME BRANCH CIRCUIT AS BLACK AND RED.
WHEN SWITCHED OFF, A TWO SECOND DELAY KEEPS THE
LOAD ON TO TEST EMERGENCY POWER. DOES NOT TEST
FEEDBACK/DIMMER OUTPUT.
RED
NORMAL NEUTRAL OR OTHER PHASE
N/A
N/A
N/A
EMERGENCY HOT
BROWN
SWITCHES OUT THE VOLTAGE PUT IN ON BROWN
EMERGENCY HOT SWITCHED TO LOAD
BLUE
N/A
EMERGENCY NEUTRAL OR OTHER PHASE
YELLOW
REMOTE TEST INPUT
(CLASS 2, DRY CONTACT INPUT)
WHITE/BLUE (GTD10DIM)
TERMINAL SCREW 4 (BLCD16DIM)
WHEN WIRING MULTIPLE UNITS TOGETHER , WHITE/BLUE OR
TERMINAL SCREW 4 MUST BE A SHARED COMMON.
TEST IS PERFORMED WHEN INPUT IS CLOSED.
WHITE/RED (GTD10DIM)
TERMINAL SCREW 3 (BLCD16DIM)
VIOLETS (GTD10DIM)
TERMINAL SCREWS 1,2
(BLCD16DIM)
FEEDBACK/DIMMER CONTACT
(DRY CONTACT OUTPUT)
OPEN WHEN NORMAL POWER IS ABSENT OR REMOTE TEST
INPUT IS CLOSED.
CLOSED WHEN NORMAL POWER IS PRESENT OR REMOTE TEST
INPUT IS OPEN.
WALL SWITCH INPUT DOES NOT TEST THIS OUTPUT.
X X
X X
Local Test Button
Normal Power LED
Load Power LED
Emergency Power LED
Remote Test Switch Input
(Dry Contact Input)
Class 2 Remote Test Input Switch
not provided.
Red
BLACK
WHITE/BLACK
Normal
Power
120-
277 V
120-
277 V
BLUE
Emergency
Power
Emergency
Load
Optional wall switch or controller to control
Emergency Load under normal conditions and
perform self-test. Cap off White/Black if not used.
YELLOW
BROWN
Feedback/Dimmer Contact
(Dry Contact Output) *
* Can be used to override 0-10V dimmer to
full brightness by breaking the positive (+)
leg or monitor status of Normal Power.
130mA @ 250V max.
W/S
2
1
4
3
BLCD16DIM
W/S
INSTALLATION
WIRING DIAGRAM
5