WIRING DESCRIPTIONS

 

BLACK

 NOTES

 

WHITE/BLACK

 

NORMAL HOT

DESCRIPTION

WIRE COLOR

 

WALL SWITCH INPUT (SELF-TEST INPUT)

  MUST BE FROM SAME BRANCH CIRCUIT AS BLACK AND RED.  

  WHEN SWITCHED OFF, A TWO SECOND DELAY KEEPS THE 

  LOAD ON TO TEST EMERGENCY POWER. DOES NOT TEST  

 

  FEEDBACK/DIMMER OUTPUT.

 

RED

  NORMAL NEUTRAL OR OTHER PHASE

   N/A

   N/A

   N/A

  EMERGENCY HOT

 BROWN

 

 SWITCHES OUT THE VOLTAGE PUT IN ON BROWN

  EMERGENCY HOT SWITCHED  TO LOAD

 BLUE

   N/A

  EMERGENCY NEUTRAL OR OTHER PHASE

 YELLOW

  REMOTE TEST INPUT

  (CLASS 2, DRY CONTACT INPUT)

 

WHITE/BLUE (GTD10DIM)    

  TERMINAL SCREW 4 (BLCD16DIM)

  WHEN WIRING MULTIPLE UNITS TOGETHER  , WHITE/BLUE OR   

  TERMINAL SCREW 4 MUST BE A SHARED COMMON. 

  TEST IS PERFORMED WHEN INPUT IS CLOSED.

 

WHITE/RED (GTD10DIM)    

  TERMINAL SCREW 3 (BLCD16DIM)

   VIOLETS (GTD10DIM)

   TERMINAL SCREWS 1,2            

 (BLCD16DIM)

  FEEDBACK/DIMMER CONTACT    

  (DRY CONTACT OUTPUT)

 

OPEN WHEN NORMAL POWER IS ABSENT OR REMOTE TEST  

 

  INPUT IS CLOSED. 

  CLOSED WHEN NORMAL POWER IS PRESENT OR REMOTE TEST    

  INPUT IS OPEN. 

  WALL SWITCH INPUT DOES NOT TEST THIS OUTPUT.

X X

X X

Local Test Button

Normal Power LED

Load Power LED

Emergency Power LED

Remote Test Switch Input

(Dry Contact Input)

Class 2 Remote Test Input Switch 

not provided.

Red

BLACK

WHITE/BLACK

Normal 

Power

120-

277 V

120-

277 V

BLUE

Emergency 

Power

Emergency 

Load

Optional wall switch or controller to control 

Emergency Load under normal conditions and

perform self-test. Cap off White/Black if not used.

YELLOW

BROWN

Feedback/Dimmer Contact

(Dry Contact Output) *

* Can be used to override 0-10V dimmer to 

full brightness by breaking the positive (+)

leg or monitor status of Normal Power.

130mA @ 250V max.

W/S

2

1

4

3

BLCD16DIM

W/S

INSTALLATION

WIRING DIAGRAM

5

Содержание GTD10DIM

Страница 1: ...ust be the same as the emergency power input voltage To reduce the risk of electrical shock fire and injury to persons 1 Disconnect all sources of power before servicing 2 Mount this device in locations and at heights where it will not be readily accessible to tampering by unauthorized personnel 3 Do not mount near gas or electric heaters 4 Do not let any wires touch hot surfaces and 5 Do not use ...

Страница 2: ...Y CONTACT GTD10DIM SPST 120 277VAC 24MA MAX 50 60HZ 120 277VAC 118MA MAX 50 60HZ 130MA 250V MAX 20A MAGNETIC BALLAST 277V 16A ELECTRONIC BALLAST 277V 10A TUNGSTEN 120V 10A MAGNETIC BALLAST 277V 10A ELECTRONIC BALLAST 277V 10A TUNGSTEN 120V MECHANICAL SPECIFICATIONS UL ACCEPTED FOR USE IN PLENUM NEMA 1 16 600V RATED 0 675 LBS BLCD16DIM 0 40 LBS GTD10DIM 35 TO 60 C 30 TO 140 F 5 TO 95 NONCONDENSING ...

Страница 3: ...E PERFORMED BY QUALIFIED PERSONNEL The GTD10DIM and the BLCD16DIM will activate an emergency lighting load automatically upon the loss of normal power If normal power is absent the status of the load cannot be overridden However if the normal power is present the emergency lighting load can be controlled by other means in order to use it as a normal lighting load depending on the wiring setup When...

Страница 4: ...e on the same branch circuit as the Black wire To use Remote Test Input the White Black wire must be de energized Input can also be sent to a controller When not using the Remote Test Input cap off the White Red and White Blue wires individually if present Utility Neutral Utility Hot Generator or Inverter Neutral Generator or Inverter Hot Automatic Transfer Switch NORMAL EMERGENCY LIGHTING Blue Y ...

Страница 5: ...EW 3 BLCD16DIM VIOLETS GTD10DIM TERMINAL SCREWS 1 2 BLCD16DIM FEEDBACK DIMMER CONTACT DRY CONTACT OUTPUT OPEN WHEN NORMAL POWER IS ABSENT OR REMOTE TEST INPUT IS CLOSED CLOSED WHEN NORMAL POWER IS PRESENT OR REMOTE TEST INPUT IS OPEN WALL SWITCH INPUT DOES NOT TEST THIS OUTPUT X X X X Local Test Button Normal Power LED Load Power LED Emergency Power LED Remote Test Switch Input Dry Contact Input C...

Страница 6: ...HE GREEN LED NORMAL POWER AVAILABLE SHOULD BE ON C THE YELLOW LED LOAD STATUS SHOULD BE OFF D THE LOAD SHOULD BE OFF E THE FEEDBACK DIMMER CONTACT SHOULD BE CLOSED TROUBLESHOOTING GUIDE ELECTRICAL SPECIFICATIONS GTD10DIM BLCD16DIM RED LED IS OFF TROUBLESHOOTING GUIDE ACTION CONDITION CHECK EMERGENCY POWER INPUT WIRING BROWN AND YELLOW WIRES AND VOLTAGE CHECK NORMAL POWER INPUT WIRING BLACK AND RED...

Отзывы: