EMERGENCY LIGHTING CONTROL DEVICE

Installation Instructions

  •  This product is intended for use with lighting fixtures controlled by an emergency panel. Any switching 
    between backup power and utility power must be done upstream of this device.
  •  All wiring connections and mounting styles must be in accordance with the National Electrical Code (NEC),  
    National Fire Protection Association (NFPA), National Electrical Safety Code, state and local codes, and any  
    other regulations set forth by the local Authority Having Jurisdiction (AHJ).
  •  Per NFPA 70E, the use of Personal Protective Equipment (PPE) may be required. Check state and local codes.
  •  The load’s operating voltage must be the same as the emergency power input voltage.
  •  To reduce the risk of electrical shock, fire, and injury to persons:

    1. Disconnect all sources of power before servicing,
    2. Mount this device in locations and at heights where it will not be readily accessible to tampering by  
    unauthorized 

personnel,

    3. Do not mount near gas or electric heaters,
    4. Do not let any wires touch hot surfaces, and
    5. Do not use outdoors (NEMA 1 rating only).
  •  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
  •  Do not use this device for other than intended use. Generator or inverter supplied emergency panel is  
    required (120 or 277 VAC, 50/60 Hz).

GTD10DIM & BLCD16DIM

CAUTION:

 

 

THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT. TO REDUCE  

     

THE RISK OF ELECTRIC SHOCK, DISCONNECT ALL POWER SOURCES BEFORE  

     

INSTALLING OR SERVICING THIS UNIT.

NOTE:

  BEFORE INSTALLING THIS DEVICE, MAKE SURE THAT THE NECESSARY BRANCH CIRCUIT WIRING IS  

AVAILABLE. AN UNSWITCHED SOURCE OF NORMAL POWER IS REQUIRED. A SEPARATE CONNECTION TO A  
GENERATOR-SUPPLIED (OR CENTRAL INVERTER SYSTEM-SUPPLIED) CIRCUIT MUST ALSO BE PROVIDED.

SERVICE BY QUALIFIED PERSONNEL ONLY

02/25/19

ALL SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL

Содержание GTD10DIM

Страница 1: ...ust be the same as the emergency power input voltage To reduce the risk of electrical shock fire and injury to persons 1 Disconnect all sources of power before servicing 2 Mount this device in locations and at heights where it will not be readily accessible to tampering by unauthorized personnel 3 Do not mount near gas or electric heaters 4 Do not let any wires touch hot surfaces and 5 Do not use ...

Страница 2: ...Y CONTACT GTD10DIM SPST 120 277VAC 24MA MAX 50 60HZ 120 277VAC 118MA MAX 50 60HZ 130MA 250V MAX 20A MAGNETIC BALLAST 277V 16A ELECTRONIC BALLAST 277V 10A TUNGSTEN 120V 10A MAGNETIC BALLAST 277V 10A ELECTRONIC BALLAST 277V 10A TUNGSTEN 120V MECHANICAL SPECIFICATIONS UL ACCEPTED FOR USE IN PLENUM NEMA 1 16 600V RATED 0 675 LBS BLCD16DIM 0 40 LBS GTD10DIM 35 TO 60 C 30 TO 140 F 5 TO 95 NONCONDENSING ...

Страница 3: ...E PERFORMED BY QUALIFIED PERSONNEL The GTD10DIM and the BLCD16DIM will activate an emergency lighting load automatically upon the loss of normal power If normal power is absent the status of the load cannot be overridden However if the normal power is present the emergency lighting load can be controlled by other means in order to use it as a normal lighting load depending on the wiring setup When...

Страница 4: ...e on the same branch circuit as the Black wire To use Remote Test Input the White Black wire must be de energized Input can also be sent to a controller When not using the Remote Test Input cap off the White Red and White Blue wires individually if present Utility Neutral Utility Hot Generator or Inverter Neutral Generator or Inverter Hot Automatic Transfer Switch NORMAL EMERGENCY LIGHTING Blue Y ...

Страница 5: ...EW 3 BLCD16DIM VIOLETS GTD10DIM TERMINAL SCREWS 1 2 BLCD16DIM FEEDBACK DIMMER CONTACT DRY CONTACT OUTPUT OPEN WHEN NORMAL POWER IS ABSENT OR REMOTE TEST INPUT IS CLOSED CLOSED WHEN NORMAL POWER IS PRESENT OR REMOTE TEST INPUT IS OPEN WALL SWITCH INPUT DOES NOT TEST THIS OUTPUT X X X X Local Test Button Normal Power LED Load Power LED Emergency Power LED Remote Test Switch Input Dry Contact Input C...

Страница 6: ...HE GREEN LED NORMAL POWER AVAILABLE SHOULD BE ON C THE YELLOW LED LOAD STATUS SHOULD BE OFF D THE LOAD SHOULD BE OFF E THE FEEDBACK DIMMER CONTACT SHOULD BE CLOSED TROUBLESHOOTING GUIDE ELECTRICAL SPECIFICATIONS GTD10DIM BLCD16DIM RED LED IS OFF TROUBLESHOOTING GUIDE ACTION CONDITION CHECK EMERGENCY POWER INPUT WIRING BROWN AND YELLOW WIRES AND VOLTAGE CHECK NORMAL POWER INPUT WIRING BLACK AND RED...

Отзывы: