STEP #1

INSTALLING THE EMERGENCY BALLAST

>  Mount the emergency ballast and battery inside the fixture.

STEP #2

INSTALLING THE TEST SWITCH

>  Install the test switch on the fixture so it can be accessed after    

fixture installation.

>  See illustration below showing basic switched and unswitched  

 

fixture connections for test switch installation. Refer to the  

 

diagrams and wire the test switch so that it removes AC power    
from both the emergency ballast and the AC ballast at the same time.

>  Drill a 1/2" hole and install the switch as shown.

STEP #3

STEP 1

STEP 2

NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label.

>  Install the CHARGING INDICATOR LIGHT  

as shown in the illustration so it will be  
visible after the fixture is installed.

INSTALLING THE CHARGING INDICATOR LIGHT

NOTE:

  Make sure that the necessary branch circuit wiring is available. An unswitched 

source of power is required. The emergency ballast must be fed from the same 
branch circuit as the AC ballast.

WARNINGS: 

1.   TO  PREVENT  DAMAGE  TO  THE  EMERGENCY  BALLAST,  JOIN  THE  BATTERY  CONNEC- 

 

TOR BEFORE SUPPLYING AC POWER TO THE EMERGENCY BALLAST.

2.  TO  PREVENT  HIGH  VOLTAGE  FROM  BEING  PRESENT  ON  RED  &  YELLOW  OUTPUT  

 

LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN  

 

INVERTER  CONNECTOR  UNTIL  INSTALLATION  IS  COMPLETE  AND  AC  POWER  IS  

 

SUPPLIED TO THE EMERGENCY BALLAST.

Fixture

Test Button

Hex Nut

Hex Nut

Test Switch

Leads

Push to Test

INSTALLATION

Charging

Indicator

Light

1/2" White

Bushing

Violet (+)

 

Brown (–)

Violet (+)

 

Brown (–)

1/2" White

Bushing

5/8" Black

Bushing

5/8" Black

Bushing

1/2" Punch

Fixture

Fixture

Charging

Indicator

Light

2

Содержание CF94

Страница 1: ...9 W 4 pin compact fluorescent lamps without integral starters 3 The emergency ballast must be connected to an unswitched AC power source 120 or 277 VAC 60 Hz 4 When installing the emergency ballast make sure all connections are in accordance with the National Electrical Code and any local regulations 5 To reduce the risk of electric shock disconnect both normal and emergency power supplies and inv...

Страница 2: ...n so it will be visible after the fixture is installed INSTALLING THE CHARGING INDICATOR LIGHT NOTE Make sure that the necessary branch circuit wiring is available An unswitched source of power is required The emergency ballast must be fed from the same branch circuit as the AC ballast WARNINGS 1 TO PREVENT DAMAGE TO THE EMERGENCY BALLAST JOIN THE BATTERY CONNEC TOR BEFORE SUPPLYING AC POWER TO TH...

Страница 3: ...Y SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL WIRING THE EMERGENCY BALLAST Determine the type of AC ballast installed in the fixture Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp See back page for more detailed wiring schematics The emergency ballast can be used with multi lamp fixtures It operates one or two lamps in the emergency...

Страница 4: ... BALLAST 22 WATT LAMP 32 WATT LAMP EMERGENCY BLACK WHT BLK INVERTER CONNECTOR EMERGENCY BALLAST RED WHITE USE PROPER TAP CAP UNUSED LEAD ORANGE BLACK WHITE 277V 120V VIOLET BROWN RED WHITE BATTERY CONNECTOR BATTERY CHARGING INDICATOR LIGHT WHT RED HOT TEST SWITCH BLK BLK WALL SWITCH 1 LAMP RAPID START BALLAST BLACK WHITE BLUE BLUE BLUE YELL BLK YELLOW RED RED RED BLU WHT LAMP COM WHT BLK INVERTER ...