5  Electrical connection

 

 

DANGER!    High voltage! Risk of electric shock! Only carry out work when the 

electrical system is disconnected from the power supply!

  INFO!

  

   Connect the compressor motor in accordance with the circuit diagram 

(see inside of terminal box).

    

    

Use suitable cable entry point of the correct protection type 

(see  name  plate)    for  routing  cables  into  the  terminal  box. 

 Insert the strain reliefs and prevent chafe marks on the cables.

    

 

 

  

Compare the voltage and frequency values with the data for the mains 

power supply. 

Only connect the motor if these values are the same.

5.1  Information for contactor and motor contactor selection

All protection devices and switching or monitoring units must be fitted in accordance with the local 
safety regulations and established specifications (e.g. VDE) as well as with the manufacturer’s infor

-

mation. 

Motor  protection  switches  are  required!

 Motor contactors, feed lines, fuses and motor 

protection switches must be rated on the basis of the maximum working current (see name plate

). 

 

For motor protection use a current-dependent and time-delayed overload protection device for moni-
toring all three phases. Set the overload protection device so that it must be actuated within 2 hours, 
if there is 1.2 times the max. working current.

5

|

 Electrical connection   

ATTENTION!  When attaching accessories with an electrical cable, a minimum 

bending radius of 3 x the cable diameter must be maintained for 

laying the cable.

Содержание HGX22e S CO2 Series

Страница 1: ...A HGX22e 125 4 S A HGX22e 160 4 A HGX22e 160 4 S A HGX22e 190 4 A HGX22e 190 4 S A BOCK HGX22e A Assembly instructions 96192 01 2021 Gb Translation of the original instructions colour the world of to...

Страница 2: ...of the compressor can result in serious or fatal injury Observe the safety instructions contained in these instructions These instructions must be passed onto the end customer along with the unit in...

Страница 3: ...service connections 4 9 Suction pipe filter and filter drier 5 Electrical connection 14 5 1 Information for contactor and motor contactor selection 5 2 Connection of the driving motor 5 3 Circuit dia...

Страница 4: ...NFO Important information or tips on simplifying work WARNING Inadequately qualified personnel poses the risk of accidents the consequence being serious or fatal injury Work on compressors is therefor...

Страница 5: ...sed in potentially explosive environments These assembly instructions describe the standard version of the compressor named in the title manufactured by Bock Bock refrigerating compressors are intende...

Страница 6: ...ation Lightweight aluminum design Suction gas cooled drive motor Name plate Fig 1 2 1 Short description Fig 2 Oil sight glass Valve plate Cylinder cover Discharge shut off valve Oil pump Terminal box...

Страница 7: ...on gas cooled X Ester oil charge HFC refrigerant e g R134a R404A R507 R407C S More powerful motor e g for air conditioning applications Lightweight aluminum design Motor variant Number of poles Swept...

Страница 8: ...he operating limits These can be found in Bock compressor selection tool VAP under vap bock de Observe the information given there Permissible ambient temperature 20 C 60 C Max permissible discharge e...

Страница 9: ...a danger of air entering on the suction side This can cause chemical reactions a pressure rise in the condenser and an elevated compressed gas temperature Prevent the ingress of air at all costs Max...

Страница 10: ...yelet Do not lift manually Use lifting gear Storage at 30 C 70 C maximum permissible relative humidity 10 95 no condensation Do not store in a corrosive dusty vaporous atmosphere or in a com bustible...

Страница 11: ...pipes with standard millimetre and inch dimensions can be used The depth of pipe insertion will depend on the dimension The connection diameters of the shut off valves are rated for maximumcompressor...

Страница 12: ...opening or closing the shut off valve release the adjustable valve spindle seal by approx of a turn counter clockwise After activating the shut off valve re tighten the adjustable valve spindle seal c...

Страница 13: ...e connec tion opened Spindle Connection open Compressor Compressor 4 Compressor assembly After activating the spindle generally fit the spindle protection cap again and tighten with 14 16 Nm This serv...

Страница 14: ...motor contactor selection All protection devices and switching or monitoring units must be fitted in accordance with the local safety regulations and established specifications e g VDE as well as wit...

Страница 15: ...lektrischer Anschluss Electrical connection Raccordement lectrique Y 96027 11 06 DGbF Niedere Spannung Low voltage Bas voltage Y Hohe Spannung High voltage Haut voltage L3 L1 L2 L3 L1 L2 Electrical co...

Страница 16: ...PTC sensor FC1 Load circuit safety switches FC2 Control power circuit fuse BP1 High pressure safety monitor BP2 Safety chain high low pressure monitoring BT3 Release switch thermostat Anschlu kasten...

Страница 17: ...1 2021 DGbFE BP1 P QA2 BP2 P L1 1 L2 1 L3 1 L1 2 N PE BT3 BT2 BT2 EB1 QA1 Main switch SF1 Control voltage switch EC1 Compressor motor QA2 Compressor contactor INT69 G Electronic trigger unit INT69 G E...

Страница 18: ...nd and remedy the cause INFO The relay switching output is executed as a floating changeover contact This electrical circuit operates according to the quiescent current principle i e the relay drops i...

Страница 19: ...e PTC connector 11 12 4 Insert PTC connector 11 12 5 Reset after mains on 11 14 5 6 External connection INT69 G BT1 Cold conductor PTC sensor motor winding BT2 Heat protection thermo stat PTC sensor E...

Страница 20: ...stallation side The compressor has undergone trials in the factory and all functions have been tested There are therefore no special running in instructions Check the compressor for transport damage D...

Страница 21: ...ause coolant to leak To prevent slugging The complete refrigeration system must be properly designed All components must be compatibly rated with each other with regard to output particularly the evap...

Страница 22: ...the following oil change service work is carried out First oil change during the first maintenance system Then after every 10 000 12 000 operating hours though no more than 3 years cleaning oil and s...

Страница 23: ...opriate hoist Dispose of the oil inside in accordance with the valid national regulations 7 Maintenance 7 4 Extract from the lubricants table The oil type filled as standard in the factory is marked o...

Страница 24: ...HG22e 190 4 A 16 5 19 8 13 8 8 0 4 8 69 40 45 HG22e 190 4 S A 16 5 19 8 16 2 9 4 5 6 87 50 47 Type 1 2 3 2 4 220 240 V 380 420 V Y 3 50 Hz 265 290 V 440 480 V Y 3 60 Hz Tolerance 10 relative to the m...

Страница 25: ...leranzen General tolerances DIN ISO 2768 mK E Ma Dimension Passung Clearance Baumustergepr ft Type examination 120 400 0 5 0 5 6 GEA Bock Gm Unbema te Radien Undimensioned radii Bearb Edited Datum Dat...

Страница 26: ...above mentioned Directive According to Annex I points 1 1 2 1 1 3 1 1 5 1 3 2 1 3 3 1 3 7 1 5 1 1 5 2 1 5 13 and 1 7 1 to 1 7 4 excepted 1 7 4 f are fulfilled Applied harmonised standards in particul...

Страница 27: ...stions about installation operation and accessories please contact our technical service or specialist wholesaler and or our representative The Bock service team can be contacted by phone 49 0 7022 94...

Страница 28: ...Bock GmbH Benzstra e 7 72636 Frickenhausen Germany Phone 49 7022 9454 0 Fax 49 7022 9454 137 www bock de Bock GmbH All rights reserved Subject to modifications Printed in Germany BOCK...

Отзывы: