•  Over the wet primer, apply a medium coat of cement to the fitting socket and pipe joint 

area.

•  Insert pipe into fitting with a slight twisting motion. Ensure that the pipe is bottomed 

into the fitting.

• Hold pipe and fitting for 30 seconds to prevent push off.

•  Wipe off excess cement. Cure time may be up to 2 hours for Ø3” pipe at 60°F. Longer 

cure time is required for larger diameter pipe and/or lower temperatures.

Note:  The vent and combustion air intake pipe/fittings must overlap a minimum 

of 1/2 inch (1.3 cm) at each joint. DO NOT drill or punch holes in the plastic pipe 

or fittings.

Condensate Drain Kit

When downward sloping of the vent system is not possible or a vertical vent arrangement 

is used, the condensate drain kit must be installed.  Follow these steps to properly install 

the kit:

• Turn off all electrical power to the water heater.

• Remove the yellow cap from the exhaust adapter.

•  Insert one end of the 3/8” OD plastic tube into the fitting on the exhaust adapter.  There 

should be a tight fit between the tube and the fitting.  If the connection is not tight, 

apply adhesive aluminum tape around the connection to secure.

•  Form a trap by looping a portion of the plastic tube into approximately a 6” diameter 

circle.  With respect to the water heater, form the loop such that it can be mounted on 

the upper 1/3 of the heater.

•  Use the supplied loop clamps and screws to secure the tubing to the side of the water 

heater and hold the loop trap in place.

•  The condensate drain tube must terminate at a proper floor drain or run to a condensate 

neutralizer (prior to the floor drain).

•  Prime the loop trap with water prior to resuming operation of the water heater.  

Disconnect the end of the tube that was connected to the exhaust adapter.  With the 

free end above the loop trap, pour water into the tube until the loop is filled halfway. 

•  Reconnect the free end to the exhaust adapter fitting and turn on electrical power to the 

water heater.

DANGER 

   Failure to prime the condensate drain loop with water will result in combustion gas 

(which may contain carbon monoxide) entering the room.  To avoid the risk of  

asphyxiation from carbon monoxide, never operate the water heater unless the 

condensate drain loop is sealed with water.

An example of this installation is shown in Figure 17.

  

Page 25

SECTION IV: INSTALLATION (cont .)

VENT & COMBUSTION AIR INTAKE (cont.)

Содержание 100-76SKG

Страница 1: ...perature limiting devices must be used on all lines to water taps WARNING Flammable vapors may be drawn to this water heater from other areas of the structure by air currents Do not store or use any f...

Страница 2: ...amage personal injury or death DANGER Water heaters utilizing Liquefied Petroleum gas LP are different from natural gas models A natural gas heater will not function safely on LP gas and vice versa To...

Страница 3: ...pecifications 4 Section II General Information 5 Section III Pre Installation 7 Section IV Installation 10 Section V Operation 30 Section VI Maintenance 33 Section VII Troubleshooting 35 Section VIII...

Страница 4: ...es and meet ANSI Z21 10 3 CSA 4 3 requirements for operation up to 180 F 82 C Approved for use as a direct vent automatic storage water heater WARNING Installation shall be in accordance with all nati...

Страница 5: ...he gas backup operation to off peak solar time can increase solar gain in the stored water TEMPERATURE CONTROL The water heater is equipped with a combination gas valve ignition control and thermostat...

Страница 6: ...TEMPERATURE AND PRESSURE RELIEF VALVE T P CAUTION To reduce the risk of excessive pressures and temperatures in this water heater install temperature and pressure protective equipment required by loca...

Страница 7: ...on will occur in the venting exhaust system It is important to not allow condensate to collect around mechanical components and bare metal parts on the water heater Therefore if condensation occurs in...

Страница 8: ...The panel must be strong enough to carry the weight of the heater when full of water NOTE Locate the heater so it is not subject to physical damage from moving vehicles or flooding Do not locate the...

Страница 9: ...nches of the top and one within 12 inches of the bottom of the enclosure These openings shall lead directly to room s of sufficient volume so that the combined volume of all the space meets the criter...

Страница 10: ...embly outlet The air intake piping is preassembled to route dilution air to the blower assembly and combustion air to the burner chamber All vent length measure ments specified in this manual are in a...

Страница 11: ...and 2 5 feet respectively The concentric vent termination is equivalent to 10 feet of straight pipe DO NOT use short bend elbows NOTE Elbows used as termination fittings must be included when determi...

Страница 12: ...5 10 67 35 10 67 3 5 30 9 14 30 9 14 3 6 25 7 62 25 7 62 4 0 85 25 91 85 25 91 4 1 80 24 38 80 24 38 4 2 75 22 86 75 22 86 4 3 70 21 34 70 21 34 4 4 65 19 81 65 19 81 4 5 60 18 29 60 18 29 4 6 55 16 7...

Страница 13: ...ting vent system Verify that the materials as specified in this manual have been used Verify the maximum and minimum vent and combustion air intake equivalent lengths and terminal clearances meet the...

Страница 14: ...hat may be opened 6 in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appliances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 6 in 15 cm for appliances...

Страница 15: ...flowing back towards the water heater CAUTION Annular spaces around vent pipe wall penetrations shall be permanently sealed using approved materials to prevent entry of combustion products into the b...

Страница 16: ...le hole through the exterior of the building is required for the vent pipe Note If air from inside the building will be used for combustion air the require ments in Section III Unconfined Space must b...

Страница 17: ...rch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 6 in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appliances 10 000 Btuh 3 kW and 100 000...

Страница 18: ...imum of 1 8 inch per foot 10 mm per meter to prevent condensate from flowing back towards the water heater CAUTION Annular spaces around vent pipe wall penetrations shall be permanently sealed using a...

Страница 19: ...hole through an exterior wall Make sure the wye concentric fitting is cemented to the large diameter pipe and that the rain cap is cemented to the small diameter pipe Install the wye concentric fittin...

Страница 20: ...of NFPA 54 ANSI Z223 1 or CSA B149 As a basic guide the following minimum clearances shall be used Minimum 12 inches 30 cm above roof Minimum 12 inches 30 cm above anticipated snow level Maximum 24 i...

Страница 21: ...ocal codes or the latest edition of NFPA 54 ANSI Z223 1 or CSA B149 As a basic guide the following minimum clearances shall be used Minimum 12 inches 30 cm above roof Minimum 12 inches 30 cm above ant...

Страница 22: ...er Dim Y Dim Y Requirements 1 Minimum 12 in 30 cm above roof US Minimum 18 in 46 cm above roof Canada 2 Minimum 12 in 30 cm above anticipated snow level US Minimum 18 in 46 cm above anticipated snow l...

Страница 23: ...l Maximum 24 inches 61 cm above roof level without additional support for vent 4 feet 1 2 m from any gable dormer or other roof structure with building interior access e g vent or window 10 feet 3 m f...

Страница 24: ...Joints WARNING Cements and primers are highly flammable Assemble joints in an adequately ventilated area away from heat sources or open flames Do not smoke Read cautions and warnings on material conta...

Страница 25: ...adhesive aluminum tape around the connection to secure Form a trap by looping a portion of the plastic tube into approximately a 6 diameter circle With respect to the water heater form the loop such...

Страница 26: ...nter check valve or pressure regulating valve is required in the cold water supply a properly sized expansion tank must be installed to control thermal expansion Do not operate the water heater in a c...

Страница 27: ...to prevent flashbacks caused by momentary pressure loss For natural gas 5 W C pressure must be maintained upstream of the gas valve during operation For LP gas a minimum of 11 W C must be maintained u...

Страница 28: ...offValve Blower Assembly ExhaustVent Slope downward and away from water heater 1 8 inch per foot max for horizontal venting Combustion Air Intake Shut Off Valve Union HeatTrap 6 min HotWater Outlet to...

Страница 29: ...replace with suitable power supply 120V 60 Hz wiring and connections The water heater draws less than 5 amps maximum Check for proper polarity at the main power connection prior to operating the wate...

Страница 30: ...Page 30 SECTION V OPERATION Figure 19 Instructions To Put The Water Heater In Operation...

Страница 31: ...12 6 0 6 16 267 6 5 48 67 25 7 6 7 6 0 1 9 9 2 20 867 21 2 5 2 7 5 3267 385 0 1 9 9 26 6 66 7 1 75 6 25 1 7 21 0 1 9 9 26 6 267 66 7 1 7 0 6 6 6 7851 2 1 8 5 7 5 3267 385 63 5525 21 285 872 2 287 5 6...

Страница 32: ...the main burner Wait 30 seconds following shut off of gas then set thermostat to the highest temperature The main burner should relight Set thermostat to the lowest temperature the main burner should...

Страница 33: ...ation ANODE RODS Anode rods should be inspected twice in the first year and at least yearly once a time interval for inspection has been developed It is recommended to check the rod s six months after...

Страница 34: ...ater heater is shut off Wait at least 5 minutes to allow the flue to cool Remove the flue baffle and clean the flue with a flexible wire brush Slide the brush down the flue at the free end of each row...

Страница 35: ...ate kit not installed vertical or horizontal vent systems 3 Contact qualified agency to install condensate kt Refer to this manual 4 Vent air intake system exceeds maximum 4 Contact qualified agency t...

Страница 36: ...UIDFH LJQLWRU DQG IODPH URG DVVHPEO QRW SRVLWLRQHG FRUUHFWO OHFWULF SRODULW WR XQLW LV LQFRUUHFW WHVW DQG FRUUHFW RZ YROWDJH WR WKH ZDWHU KHDWHU 6XSSO YROWDJH PXVW HTXDO UDWHG YROWDJH KHFN WKH YHQW DQ...

Страница 37: ...ner Door Left Side 2 Flue Baffle 12 Air Intake Boot 3 Hot Outlet Nipple 1 x 4 5 13 Trim Plate 4 Dip Tube 14 PVC Pipe 3 x 62 5 5 Anode Rods 15 PVC Tee 3 x 3 x 2 6 T P Relief Valve 16 PVC Pipe 2 x 3 7 C...

Страница 38: ...FG APPR Q A SHEET 1 OF 1 WEIGHT COMMENTS THE INFORMATION CONTAINED INTHIS DRAWING ISTHE SOLE PROPERTY OF BOCKWATER HEATERS INC ANY REPRODUCTION IN PART OR AS AWHOLE WITHOUTTHEWRITTEN PERMISSION OF BOC...

Страница 39: ...ively for commercial uses Tank and Heat Exchanger We also warrant that the tank and heat exchanger will not leak due to defective materials or workmanship for five years from the date of original inst...

Страница 40: ...somewhere else Fail to follow the care and maintenance instructions provided with the water heater Remove the anode rods Fail to inspect and replace the anode rods you must retain and present your pa...

Отзывы: