1) In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2) In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
3) If locally adopted installation codes specify clearances different than those illustrated, then the most stringent clearance shall prevail.
†  A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves 

both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Manufacturer’s recommendation. Must be in accordance with local installation codes and requirements of the gas supplier.

In addition to the clearances specified, the following items shall be accounted for during installation:
•  Do not terminate near soffit vents or crawl space or other area where condensate or vapor could create a 

nuisance hazard or cause property damage.

•  Do not locate the exhaust vent terminal where condensate or vapor could cause damage or could be 

detrimental to the operation of regulators, relief valves, or other equipment.

•  Do not locate the exhaust vent terminal over public area or walkways where condensate or vapor can 

cause nuisance or hazard.

•  Do not locate the vent terminal in proximity to plants/shrubs.
•  The vent and air intake shall terminate a minimum of 12” (30.5 cm) above expected snowfall level to 

prevent blockage.

CAUTION  

 

Never install air intake terminal above vent (exhaust) terminal. 

Page 14 

SECTION IV: INSTALLATION (cont .)

VENT & COMBUSTION AIR INTAKE (cont.)

Table 8: Direct Vent Terminal Clearances

Canadian Installations

1

US Installations

2

A = Clearance above grade, veranda, 

porch, deck, or balcony

12 inches (30 cm)

12 inches (30 cm)

B = Clearance to window or door that 

may be opened

6 in (15 cm) for appliances 

 10,000 

Btuh (3 kW), 12 in (30 cm) for 

appliances > 10,000 Btuh (3 kW) and 

 100,000 Btuh (30 kW), 36 in (91 

cm) for appliances > 100,000 Btuh 

(30 kW)

6 in (15 cm) for appliances 

 10,000 

Btuh (3 kW), 9 in (23 cm) for 

appliances > 10,000 Btuh (3 kW) and 

 50,000 Btuh (15 kW), 12 in (30 cm) 

for appliances > 50,000 Btuh (15 kW)

C = Clearance to permanently closed 

window

12 inches (30 cm)

*

12 inches (30 cm)

*

D = Vertical clearance to ventilated 

soffit located above the terminal within 

a horizontal distance of 2 feet (61 cm) 

from the centerline of the terminal

12 inches (30 cm)

*

12 inches (30 cm)

*

E = Clearance to unventilated soffit

12 inches (30 cm)

*

12 inches (30 cm)

*

F = Clearance to outside corner

2 ft (60 cm)

*

2 ft (60cm)

*

G = Clearance to inside corner

18 in (45 cm)

*

18 in (45 cm)

*

H = Clearance to each side of centerline 

extended above meter/regulator 

assembly

3 ft (91 cm) within a height  

of 15 ft (4.6 m)

*

Clearance in accordance with local 

installation codes and the require-

ments of the gas supplier.

I = Clearance to service regulator vent 

outlet

3 ft (91 cm)

Clearance in accordance with local 

installation codes and the require-

ments of the gas supplier.

J = Clearance to non-mechanical 

air supply inlet to building or the 

combustion air inlet to any other 

appliance

6 in (15 cm) for appliances 

 10,000 

Btuh (3 kW), 12 in (30 cm) for 

appliances > 10,000 Btuh (3 kW) and 

 100,000 Btuh (30 kW), 36 in (91 

cm) for appliances > 100,000 Btuh 

(30 kW)

6 in (15 cm) for appliances 

 10,000 

Btuh (3 kW), 9 in (23 cm) for 

appliances > 10,000 Btuh (3 kW) and 

 50,000 Btuh (15 kW), 12 in (30 cm) 

for appliances > 50,000 Btuh (15 kW)

K = Clearance to a mechanical air 
supply inlet

6 feet (1.83 m)

3 feet (91 cm) above if within  

10 feet (3 m) horizontally

L = Clearance above paved sidewalk 

or paved driveway located on public 

property

7 feet (2.13 m)†

Cannot be located above public 

walkways or other areas where 

condensate or vapor can cause 

nuisance or hazard.

M = Clearance under veranda, porch, 
deck, or balcony

12 inches (30 cm) ‡

12 inches (30 cm) ‡

Содержание 100-76SKG

Страница 1: ...perature limiting devices must be used on all lines to water taps WARNING Flammable vapors may be drawn to this water heater from other areas of the structure by air currents Do not store or use any f...

Страница 2: ...amage personal injury or death DANGER Water heaters utilizing Liquefied Petroleum gas LP are different from natural gas models A natural gas heater will not function safely on LP gas and vice versa To...

Страница 3: ...pecifications 4 Section II General Information 5 Section III Pre Installation 7 Section IV Installation 10 Section V Operation 30 Section VI Maintenance 33 Section VII Troubleshooting 35 Section VIII...

Страница 4: ...es and meet ANSI Z21 10 3 CSA 4 3 requirements for operation up to 180 F 82 C Approved for use as a direct vent automatic storage water heater WARNING Installation shall be in accordance with all nati...

Страница 5: ...he gas backup operation to off peak solar time can increase solar gain in the stored water TEMPERATURE CONTROL The water heater is equipped with a combination gas valve ignition control and thermostat...

Страница 6: ...TEMPERATURE AND PRESSURE RELIEF VALVE T P CAUTION To reduce the risk of excessive pressures and temperatures in this water heater install temperature and pressure protective equipment required by loca...

Страница 7: ...on will occur in the venting exhaust system It is important to not allow condensate to collect around mechanical components and bare metal parts on the water heater Therefore if condensation occurs in...

Страница 8: ...The panel must be strong enough to carry the weight of the heater when full of water NOTE Locate the heater so it is not subject to physical damage from moving vehicles or flooding Do not locate the...

Страница 9: ...nches of the top and one within 12 inches of the bottom of the enclosure These openings shall lead directly to room s of sufficient volume so that the combined volume of all the space meets the criter...

Страница 10: ...embly outlet The air intake piping is preassembled to route dilution air to the blower assembly and combustion air to the burner chamber All vent length measure ments specified in this manual are in a...

Страница 11: ...and 2 5 feet respectively The concentric vent termination is equivalent to 10 feet of straight pipe DO NOT use short bend elbows NOTE Elbows used as termination fittings must be included when determi...

Страница 12: ...5 10 67 35 10 67 3 5 30 9 14 30 9 14 3 6 25 7 62 25 7 62 4 0 85 25 91 85 25 91 4 1 80 24 38 80 24 38 4 2 75 22 86 75 22 86 4 3 70 21 34 70 21 34 4 4 65 19 81 65 19 81 4 5 60 18 29 60 18 29 4 6 55 16 7...

Страница 13: ...ting vent system Verify that the materials as specified in this manual have been used Verify the maximum and minimum vent and combustion air intake equivalent lengths and terminal clearances meet the...

Страница 14: ...hat may be opened 6 in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appliances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 6 in 15 cm for appliances...

Страница 15: ...flowing back towards the water heater CAUTION Annular spaces around vent pipe wall penetrations shall be permanently sealed using approved materials to prevent entry of combustion products into the b...

Страница 16: ...le hole through the exterior of the building is required for the vent pipe Note If air from inside the building will be used for combustion air the require ments in Section III Unconfined Space must b...

Страница 17: ...rch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 6 in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appliances 10 000 Btuh 3 kW and 100 000...

Страница 18: ...imum of 1 8 inch per foot 10 mm per meter to prevent condensate from flowing back towards the water heater CAUTION Annular spaces around vent pipe wall penetrations shall be permanently sealed using a...

Страница 19: ...hole through an exterior wall Make sure the wye concentric fitting is cemented to the large diameter pipe and that the rain cap is cemented to the small diameter pipe Install the wye concentric fittin...

Страница 20: ...of NFPA 54 ANSI Z223 1 or CSA B149 As a basic guide the following minimum clearances shall be used Minimum 12 inches 30 cm above roof Minimum 12 inches 30 cm above anticipated snow level Maximum 24 i...

Страница 21: ...ocal codes or the latest edition of NFPA 54 ANSI Z223 1 or CSA B149 As a basic guide the following minimum clearances shall be used Minimum 12 inches 30 cm above roof Minimum 12 inches 30 cm above ant...

Страница 22: ...er Dim Y Dim Y Requirements 1 Minimum 12 in 30 cm above roof US Minimum 18 in 46 cm above roof Canada 2 Minimum 12 in 30 cm above anticipated snow level US Minimum 18 in 46 cm above anticipated snow l...

Страница 23: ...l Maximum 24 inches 61 cm above roof level without additional support for vent 4 feet 1 2 m from any gable dormer or other roof structure with building interior access e g vent or window 10 feet 3 m f...

Страница 24: ...Joints WARNING Cements and primers are highly flammable Assemble joints in an adequately ventilated area away from heat sources or open flames Do not smoke Read cautions and warnings on material conta...

Страница 25: ...adhesive aluminum tape around the connection to secure Form a trap by looping a portion of the plastic tube into approximately a 6 diameter circle With respect to the water heater form the loop such...

Страница 26: ...nter check valve or pressure regulating valve is required in the cold water supply a properly sized expansion tank must be installed to control thermal expansion Do not operate the water heater in a c...

Страница 27: ...to prevent flashbacks caused by momentary pressure loss For natural gas 5 W C pressure must be maintained upstream of the gas valve during operation For LP gas a minimum of 11 W C must be maintained u...

Страница 28: ...offValve Blower Assembly ExhaustVent Slope downward and away from water heater 1 8 inch per foot max for horizontal venting Combustion Air Intake Shut Off Valve Union HeatTrap 6 min HotWater Outlet to...

Страница 29: ...replace with suitable power supply 120V 60 Hz wiring and connections The water heater draws less than 5 amps maximum Check for proper polarity at the main power connection prior to operating the wate...

Страница 30: ...Page 30 SECTION V OPERATION Figure 19 Instructions To Put The Water Heater In Operation...

Страница 31: ...12 6 0 6 16 267 6 5 48 67 25 7 6 7 6 0 1 9 9 2 20 867 21 2 5 2 7 5 3267 385 0 1 9 9 26 6 66 7 1 75 6 25 1 7 21 0 1 9 9 26 6 267 66 7 1 7 0 6 6 6 7851 2 1 8 5 7 5 3267 385 63 5525 21 285 872 2 287 5 6...

Страница 32: ...the main burner Wait 30 seconds following shut off of gas then set thermostat to the highest temperature The main burner should relight Set thermostat to the lowest temperature the main burner should...

Страница 33: ...ation ANODE RODS Anode rods should be inspected twice in the first year and at least yearly once a time interval for inspection has been developed It is recommended to check the rod s six months after...

Страница 34: ...ater heater is shut off Wait at least 5 minutes to allow the flue to cool Remove the flue baffle and clean the flue with a flexible wire brush Slide the brush down the flue at the free end of each row...

Страница 35: ...ate kit not installed vertical or horizontal vent systems 3 Contact qualified agency to install condensate kt Refer to this manual 4 Vent air intake system exceeds maximum 4 Contact qualified agency t...

Страница 36: ...UIDFH LJQLWRU DQG IODPH URG DVVHPEO QRW SRVLWLRQHG FRUUHFWO OHFWULF SRODULW WR XQLW LV LQFRUUHFW WHVW DQG FRUUHFW RZ YROWDJH WR WKH ZDWHU KHDWHU 6XSSO YROWDJH PXVW HTXDO UDWHG YROWDJH KHFN WKH YHQW DQ...

Страница 37: ...ner Door Left Side 2 Flue Baffle 12 Air Intake Boot 3 Hot Outlet Nipple 1 x 4 5 13 Trim Plate 4 Dip Tube 14 PVC Pipe 3 x 62 5 5 Anode Rods 15 PVC Tee 3 x 3 x 2 6 T P Relief Valve 16 PVC Pipe 2 x 3 7 C...

Страница 38: ...FG APPR Q A SHEET 1 OF 1 WEIGHT COMMENTS THE INFORMATION CONTAINED INTHIS DRAWING ISTHE SOLE PROPERTY OF BOCKWATER HEATERS INC ANY REPRODUCTION IN PART OR AS AWHOLE WITHOUTTHEWRITTEN PERMISSION OF BOC...

Страница 39: ...ively for commercial uses Tank and Heat Exchanger We also warrant that the tank and heat exchanger will not leak due to defective materials or workmanship for five years from the date of original inst...

Страница 40: ...somewhere else Fail to follow the care and maintenance instructions provided with the water heater Remove the anode rods Fail to inspect and replace the anode rods you must retain and present your pa...

Отзывы: