2. INTRODUCTION & SPECIFICATION

 

This heater produces a totally dry heat, no condensation, no gas, no fumes. It reaches maximum heat output within a minute from being turned on 
and has an internal thermostat. It is quick and easy to install reducing installation costs. Used with the CS-7 controller it can provide low / high heat 
or fan only settings. 

Model 

SCHG-45T 

Power 

4500W 

Input supply 

220-240V 

Dimensions (W x D x H) 

594 x 594 x 153mm 

Weight 

10kg 

Recommended Mounting Height 

2.5 - 3.0M 

Safety Distance from Heater 

1.5M 

Optional Controller Model Number 

CS-7 

 

3. MOUNTING INSTALLATION 

3.1 

CEILING MOUNTING 

The heater is intended for installation in a suspended ceiling mounted within or on the 'tee' bar supports. For optimum results do not fit in ceilings 
higher than 3m. As air is only introduced through the front of the unit the heater may be sighted anywhere. The air intake and discharge areas must 
be kept completely clear for a minimum of 1.5m from the front of the heater. In an area using multiple units, heaters should be spread to provide an 
even heat distribution. 

 

IMPORTANT! 

A  minimum  clearance  of  205mm  is  needed  between  the  bottom  of  the  false  ceiling  and  the  original  roof/ceiling  to  allow 

installation of the heater. 

 

IMPORTANT! 

DO NOT cover the heater case with any insulation. It must be left with nothing touching the metal case. 

 

IMPORTANT! 

DO NOT use plastic type diffusers as these may be damaged by the heat. 

 

IMPORTANT!

 Ensure that the mounting surface / ceiling supports are capable of taking the additional  weight of the heater there are 2 eye 

hooks supplied with the heater that should be used if additional support of the heater is required. 
When using the diffuser the four Z brackets provided should be attached to the side of the heater to enable the heater to be supported by the 'tee' 
bar and immediately above the diffuser. 

4.  ELECTRICAL CONNECTIONS 

4.1 

230V SINGLE PHASE 

– Without controls. 

Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing. 
Drawings show connections inside the black terminal box on the outside of the heater. 

Do NOT use power tools to undo or do up terminal screws.

 

Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes. 
 

 

Standard Connection and Use 
 
 
Use 2.5mm² 3 Core Mains Cable (see note above). 
Connect Brown wire 

– Terminal L. 

Connect Blue wire 

– Terminal N. 

Connect Green / Yellow wire 

– Terminal E or 

 
 
 

Ensure the 3 links 

 are in position in the Control Box as shown in drawing to the 

left. Links should be between terminals 1 and 2, 3 and 4, 4 and 5. 
 
 
 

PLEASE  CHECK  ALL  CONNECTIONS  BEFORE  TURNING  ON  AS  INCORRECT 
WIRING IS NOT COVERED BY THE GUARANTEE 
 

 

 

De-Rating the Heater 
 
 
If you wish to de-rate the heater from 4.5kW to 2.25kW remove the link 

between terminal 4 and terminal 5 in 

the Control Box. 
Ensure you tighten up the screws after removing the link. See drawing to the Right. 

 

 
 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE 

GUARANTEE.

 

 

CS-7 Controller 

(Optional Extra) 

Heater de-rated 

to 2.25kW 