21. SETTING THE LOCKOUT FEATURES.
The PROSTAT2 comes with a lockout feature which enables the installer to disable certain functions of the
thermostat to a complete lockdown depending on the mode selected. This can be useful if using the Thermostat in
a public area to stop certain buttons / modes from operating.
Setting the Installer lockout mode
1. Switch the slider to
OFF
. Press and keep holding the
A
and
H
buttons together (under the fascia), now press
the
Next
button and the technical settings menu will be displayed. Release all buttons.
2. Press the
Next
button until you get to
SER
(CODE) Settings. A numeric password will be required to enter
this section. The factory default password is 0000.
N.B. The screen will display Err if the incorrect password is entered.
3. Press
+
/
–
to enter the first digit of the password. Press the
H
button to move to the next digit. Repeat this until
all 4 digits have been entered.
4. Press the
Next
button until you get to
Pro Part
(Lockout mode).
5. Use the
+
/
–
buttons to choose between:-
Default Setting 1
This mode works as a standard Programmable Room Thermostat.
Partial Lockout 2
This mode allows the installer to set the Maximum temperature Setpoint (factory default 21°c) and allows the end
user to adjust all other settings apart from maximum temperature set point.
Partial Lockout 3
This mode allows the installer to set the Maximum temperature Setpoint (factory default 21°c) and locks all
keys/slider except, to change the time and date, off (frost protection) and allow temporary manual override
(temperature Up / Down arrows).
Partial Lockout 4
This mode allows the installer to set the Maximum temperature Setpoint (factory default 21°c) and l ocks all
keys/slider except from off (frost protection) and allow temporary manual override (temperature Up / Down arrows).
Full Lockout 5
This mode locks all keys / slider. The End user cannot adjust anything.
Setting the Maximum Program Temperature
Press the
Next
button until you get to
Pro tenp
.
Press the
+
/
–
buttons to
adjust the maximum temperature in 0.5⁰C steps.
Note:- If you have exited the installer lockout features repeat steps 1-3 above.
6. To exit the Installer Menu, press the
Home
Button.
Number
Time / Date
Program
Permanent
Manual
Override
Temp
Manual
Override
All Day
Holiday
1
✓
✓
✓
✓
✓
✓
2
✓
✓
✓
*
✓
*
✓
*
✓
*
3
✓
✗
✗
✓
*
✗
✗
4
✗
✗
✗
✓
*
✗
✗
5
✗
✗
✗
✗
✗
✗
N.B.
*Temperature can only be adjusted up to the maximum temperature setpoint.
(21⁰C Default)
NOTE: It is our policy to continually improve products and as such we reserve the right to alter data, specifications and
component parts without prior notice.
REGISTER:
Activate
your
warranty
by
registering
online
at
www.bnthermic.co.uk and retain this installation data for future reference
IMPORTANT:
No liability is accepted for incorrect use of this product.
WARRANTY:
Your BN Thermic product is guaranteed for one year from
date of purchase. We will repair or replace at our discretion any part found to
be defective. We cannot assume any consequential liability. This guarantee
in no way prejudices your rights under common law and is offered as an
addition to consumer liability rights.
PROTIM2INS-v01
This product conforms to EU Directive 2002/96/EC.
This appliance bears the symbol of the crossed waste bin. This indicates that, at the end of its useful life, it must not
be disposed of as domestic waste, but must be taken to a collection centre for waste electrical and electronic
equipment. It is the user's responsibility to dispose of this appliance through the appropriate channels. Failure to do
so may incur penalties established by laws governing waste disposal.
BN Thermic Ltd,
34 Stephenson Way,
Crawley, RH10 1TN
Tel: +44 (0) 1293 547361
Email: [email protected]