6 .   C O N N E C T I N G   C O N T R O L S   T O   T H E   AI R   C U R T AI N

 

 

6.1  Adding  a  Tamperproof  (RST-TP)  or  Standard  Thermostat  (RST2-IN).  Fan  runs  continuously  and  heat  turns  on  /  off 

with thermostat 

 

Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing. 
Drawings show connections inside the black terminal box on the outside of the air curtain and the inside of the RST-TP or RST2-IN Thermostat. 
Other thermostats may be used BUT they must be suitable for a minimum 6A load.

 Do NOT use power tools to undo or do up terminal screws.

  

Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes. 

 

Standard Connection using RST-TP Thermostat 

 

Use 0.75mm² 4 Core Cable to connect the air curtain to the thermostat (see note above). 

 

Remove link 

in air curtain terminal box between terminals 2 and 3. Ensure the remaining 2 links are in position as shown above. 

 

Air curtain (Control Box) to Thermostat Cable

– (Colours for reference only) 

Connect Brown wire 

– Terminal 1 or L of air curtain and Terminal 3 of Thermostat.  

Connect Grey wire 

– Terminal 3 of air curtain and Terminal 1 of Thermostat. 

Connect Blue wire 

– Terminal 5 or N of air curtain and Terminal 4 or N of Thermostat.  

Connect Green / Yellow wire 

– Terminal E or 

of air curtain and earth connection on Thermostat. 

 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE 

 

6.2  Adding a Programmable Timer (PROTIM-7). 

 

Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing.  
Drawings show connections inside the black terminal box on the outside of the air curtain and the inside of the CS-7 Controller. 

Do NOT use power 

tools to undo or do up terminal screws.

 

Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes. 

 

Standard Connection using a PROTIM-7 Timer. 

Use 0.75mm² 4 Core Cable to connect the air curtain to the PROTIM-7 Timer (see note above). 
Remove link 

in air curtain terminal box between terminals 1 and 2. Ensure the remaining 2 links are in position as shown above. 

 

Air curtain (Control Box) to PROTIM-7 Timer Cable

– (Colours for reference only) 

Connect Brown wire 

– Terminal 1 or L of air curtain and Terminal L on Timer. 

Add 0.75mm² Link wire between Terminal L on Timer and Terminal Sin on Timer 
Connect Grey wire 

– Terminal 2 of air curtain and Terminal Sout on Timer. 

Connect Blue wire 

– Terminal 5 or N of air curtain and Terminal N on Timer. 

Connect Green / Yellow wire 

– Terminal E or 

of air curtain and earth connection (Terminal E) on Timer. 

 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE

 

 

Содержание CAT-90

Страница 1: ...an The unit should be protected by a suitably rated isolator and fuse or MCB This air curtain is IP20 rated and is suitable for indoor or under cover use only Do not attach this air curtain to an exte...

Страница 2: ...2 x M5 Lock washers 4 x M4 Nuts and 4 x M4 Washers 4 2 WALL MOUNTING ABOVE A DOORWAY Attach the two Small wall mounting brackets to the air curtain using the Plastic Domes and M2 9 Screws Make sure bo...

Страница 3: ...n switch back to the fuse board use 10mm cable Drawings show connections inside the black terminal box on the outside of the air curtain Do NOT use power tools to undo or do up terminal screws Please...

Страница 4: ...the power supply box Use minimum 1 5mm 5 Core Mains Cable see note above Connect Brown wire Terminal 1 or L Connect Black wire Terminal 2 Connect Grey wire Terminal 3 Connect Blue wire Terminal 5 or N...

Страница 5: ...low wire Terminal E or of air curtain and earth connection on Thermostat PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE 6 2 Adding a Programmable Ti...

Страница 6: ...the air curtain to the CS 7 Controller see note above Remove any links that may be present in air curtain Control Box between terminals 1 2 3 4 or 5 Air curtain Control Box to CS 7 Controller Cable C...

Страница 7: ...s for reference only Move the Dark Brown link cable from the centre switch terminal 1 to the centre switch terminal 3 shown above by dark brown wire Connect Brown wire Terminal 1 or L of air curtain a...

Страница 8: ...gn materials around the airways If the air curtain fails to operate or the safety cut out operates again turn off the air curtain and contact a qualified electrician The Air curtain is protected by a...

Отзывы: