5.2 230V SINGLE PHASE
– With Thermostat (RST-TP). Fan runs continuously and heat turns on / off with thermostat.
Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing.
Drawings show connections inside the black terminal box on the outside of the air curtain and the inside of the RST-TP Thermostat. Other
thermostats may be used BUT they must be suitable for a 10A Load.
Do NOT use power tools to undo or do up terminal screws.
Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes.
Standard Connection using RST-TP Thermostat
Use 4mm² 3 Core Mains Cable (see note
above)
Use 1.5mm² 4 Core Cable to connect the air
curtain to the thermostat (see note above).
Remove link
in air curtain
terminal box between terminals 2 and 3.
Ensure the remaining 2 links are in position
as shown in drawing to the left.
Mains Cable (Power supply box)
Connect Brown wire
– Terminal 1 or L.
Connect Blue wire
– Terminal 5 or N.
Connect Green / Yellow wire
– Terminal E
or
Air curtain to Thermostat Cable
– (Colours for reference only)
Connect Brown wire
– Terminal 1 or L of air curtain and Terminal 3 of Thermostat.
Connect Grey wire
– Terminal 3 of air curtain and Terminal 1 of Thermostat.
Connect Blue wire
– Terminal 5 or N of air curtain and Terminal 4 or N of Thermostat.
Connect Green / Yellow wire
– Terminal E or
of air curtain and earth connection on Thermostat.
If you wish to de-rate the air curtain from 6kW to 4kW remove the link
between terminal 3 and terminal 4. Ensure you tighten up the
screws after removing the link.
PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE
5.3 230V SINGLE PHASE
– With CS-7 Controller (CS-7 Controller provides on / off / high heat / low heat / fan only settings).
Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing.
Drawings show connections inside the black terminal box on the outside of the air curtain and the inside of the CS-7 Controller.
Do NOT use power
tools to undo or do up terminal screws.
Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes.
Standard Connection using CS-7 Controller
Use 4mm² 3 Core Mains Cable (see note above).
Use 1.5mm² 5 Core Cable to connect the air curtain to the CS-7 Controller (see note above).
Remove any links
that may be present in air curtain terminal box between terminals 1,2,3,4 or 5.
Mains Cable (Power supply box)
Connect Brown wire
– Terminal 1 or L. Connect Blue wire – Terminal 5 or N.
Connect Green / Yellow wire
– Terminal E or
Air curtain to CS-7 Controller Cable
– (Colours for reference only)
Connect Brown wire
– Terminal 1 or L of air curtain and Top Terminal L2 (Supply) on right DP Switch of CS-7.
Connect Grey wire
– Terminal 2 of air curtain and Centre Switch Terminal 1 of CS-7.
Connect Blue wire (adding red or another suitable colour sleeve to both ends first)
– Terminal 3 of air curtain and Terminal 1 on Left SP Switch of CS-7.
Connect Black wire
– Terminal 4 of air curtain and Terminal 2 on left SP Switch of CS-7.
Connect Green / Yellow wire
– Terminal E or
of air curtain and earth connection on CS-7.
PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE