SFU-0302 SSE
M a n u a l
– 24–
BMR GmbH
2014-03-17
E
Error Description
Cause
Fixing
Incorrect connection cable or wiring
fault
> Check cable for proper Pinout.
> Verify at USB cables that it's length is not
longer than 2m
> Try to use original BMR cables, only.
In case of using RS232
> Use the USB-Interface at the PC together
with a USB-RS232 converter.
> For use with SFU 0303 a specific RS232
cable is required
In case of using a USB-RS232
converter the USB-driver is not
installed correctly.
install driver
In case of connecting the
converter with a PC or
after launching the SW
SFU-Terminal the
Converter is not
detected and not
recognized
unsure
Restart SFU-Terminal
Start with push buttons
not possible
Start button deactivated
Enable Start button by un-checking the
checkbox "Block Start Button"
An input is assigned with the function
Emergency Stop and configured as
"Low Active".
> This is default state on delivery
> For unlocking, a signal of "HI" / +24V is
required at this input
> Deactivate this function or setup as "High
Active"
The evaluation of the temperature
sensor is activated in the spindle
characteristic, but it is not connected
or a sensor isn't implemented within
the spindle
-> in this case Error is indicated,
additionally
> Connect the temp sensor wires with the
SFU .
> un-check the button "Temp Sensor" in the
spindle characteristic in SFU-Terminal
Spindle does not start,
in spite of a valid signal
for Start
The spindle test is engaged
> Check cable and connections for proper
wiring or short circuit
> Check spindle
Содержание SFU-0302-SSE
Страница 1: ...Frequency Converter SFU 0302 SSE ...
Страница 5: ...SFU 0302 SSE M a n u a l 5 BMR GmbH 2014 03 17 E 3 Block Diagram ...
Страница 6: ...SFU 0302 SSE M a n u a l 6 BMR GmbH 2014 03 17 E ...
Страница 13: ...SFU 0302 SSE M a n u a l 13 BMR GmbH 2014 03 17 E 6 5 Screw Terminals figure 1 Mains Spindle screw terminals ...
Страница 28: ...SFU 0302 SSE M a n u a l 28 BMR GmbH 2014 03 17 E 13 Mechanics Views Dimensions ...
Страница 29: ...SFU 0302 SSE M a n u a l 29 BMR GmbH 2014 03 17 E this page is left intentionally left blank ...