1

Tel: +420 774 415 703

Fax: +420 494 533 602

[email protected]

www.bmr-trading.com

Содержание HM2006

Страница 1: ...ler User and service manual version 1 3 BMR BMR trading Lipovka 17 Horní lán 17 516 01 Rychnov n Kn 779 00 Olomouc Czech Republic Czech Republic 1 Tel 420 774 415 703 Fax 420 494 533 602 export bmr trading com www bmr trading com ...

Страница 2: ...splaying mode 4 4 2 Absolute value displaying mode 4 4 3 Programming mode 5 4 4 Manual control mode 5 5 Adjustable parameters 5 6 Comment to parameter setting 7 7 Installation 7 8 Technical features 7 9 Connection diagrams 9 BMR BMR trading Lipovka 17 Horní lán 17 516 01 Rychnov n Kn 779 00 Olomouc Czech Republic Czech Republic 2 Tel 420 774 415 703 Fax 420 494 533 602 export bmr trading com www b...

Страница 3: ...te internal generator of pulses in the regulator itself Afterwards it is necessary to tune real time of regulator clock with time of switching clock of main energy meter and keep regular control There is also possibility to use one regulator input for tariff pulse which is at some tariff rates needed for differentiation between technical and regulation maximum If there is no possibility to connect...

Страница 4: ... mode 4 Working mode description 4 1 Actual value displaying mode It is basic mode in which device is situated after connection of supply voltage In this mode it is possible to select displaying of one from four values 1 actual measured consumption value calculated on average hour power 2 current time hour minute with automatic changing of summer time and back 3 current date day month 4 instantane...

Страница 5: ... appears on the display again It is possible to move to another parameter or by pressing the button SET to escape to the basic mode If there is no action at the keyboard for 1 minutes device automatically returns back to the basic mode Parameter description and their settings are explained in chapter No 5 4 4 Manual control mode This mode is used for manual control of power demand without automati...

Страница 6: ...ction min 0 15 0 r_C Regulation constants for regulation curve see graph of regulation principle P1 Threshold value of limitation curve for relay disconnecting 0 80 0 P2 Threshold value of limitation curve for relay connection 0 80 10 HYSt Hysteresis zone of protection against maximum regulated value overrun 5 20 10 YEAr Actual year setting 2002 dAt Actual date setting Set parameter is blinking 01...

Страница 7: ...006 is designed in plastic box with size of 6 modules for DIN rail mounting Connection to the separation optoelectronic unit is shown on the connection diagrams below chapter 9 Minimum needed setting 1 Transition constant for pulse inputs this value can be found on the energy meeter For example 1 pulse 0 1 kWh it means that 1 pulse has weight of 100 Wh Value 100 set into parameter P_C P_C1 Wh imp ...

Страница 8: ...also parameters DAT and YEAr 8 Technical features Parameter Value Supply voltage 230 VAC 50 Hz 10 15 Frequency 50 60 Hz Power consumption 4 VA Number of signal inputs 5 Internal power supply for signal inputs 12 VDC Number of output channels 6 Load capability of relay contacts 250 VAC 3 A Communication RS485 Communication speed 9600 baud Communication line distance 1200 m Working temperature 25 C ...

Страница 9: ...trolled by positive pulse Picture 4 Connection diagram of HM2006 inputs controlled by positive pulse from external power supply BMR BMR trading Lipovka 17 Horní lán 17 516 01 Rychnov n Kn 779 00 Olomouc Czech Republic Czech Republic 9 Tel 420 774 415 703 Fax 420 494 533 602 export bmr trading com www bmr trading com ...

Страница 10: ...of systems for measurement and control BMR BMR trading Lipovka 17 Horní lán 17 516 01 Rychnov n Kn 779 00 Olomouc Czech Republic Czech Republic 10 Tel 420 774 415 703 Fax 420 494 533 602 export bmr trading com www bmr trading com ...

Страница 11: ...of systems for measurement and control BMR BMR trading Lipovka 17 Horní lán 17 516 01 Rychnov n Kn 779 00 Olomouc Czech Republic Czech Republic 11 Tel 420 774 415 703 Fax 420 494 533 602 export bmr trading com www bmr trading com ...

Страница 12: ...of systems for measurement and control BMR BMR trading Lipovka 17 Horní lán 17 516 01 Rychnov n Kn 779 00 Olomouc Czech Republic Czech Republic 12 Tel 420 774 415 703 Fax 420 494 533 602 export bmr trading com www bmr trading com ...

Отзывы: