background image

USB-AD-OEM 

 

 

Page 8 

5

 

Important Notes for Using the USB-AD-OEM 

 

The device is only suitable for extra-low voltages – please observe the relevant regulations! Only 
use the device with housing closed. ESD voltages at open lines may cause malfunction. 

 

Only use non-solvent detergents for cleaning. The product is designed to be maintenance-free. 

 

Signal cables are connected at the 40-way pin connector – preferably use shielded cables. For 
best  possible  interference  suppression,  connect  shield  at  one  end  only.  Close  open  inputs  if 
necessary. 

 

Connect the earth of the board with the functional earth. Be sure to avoid ground loops since they 
will cause measuring errors! 

 

PCs (notebooks) which are not grounded often produce high potentials to earth at the USB socket 
so that safe operation cannot be guaranteed. Connect the measuring system to earth in this case. 

 

The gain is adjusted to even values. Therefore, only 4000 values (for 12 bit) of the full range of the 
converter are used. As a result, the measuring ranges are slightly larger (e.g. 

±

5.12V) than the 

indicated measuring ranges so that overranges can be recognized. The AD converter of the USB-
AD-OEM has a code noise of up to 

±

1 LSB 

 

The device must not be used for safety-relevant tasks. With the use of the product, the customer 
becomes manufacturer by law and is therefore fully responsible for the proper installation and use 
of the product. In the case of improper use and/or unauthorized interference, our warranty ceases 
and any warranty claim is excluded. 

 

Do not dispose of the product in the domestic waste or at any waste collection places. It has to be 
either duly disposed according to the WEEE directive or can be returned to bmcm at your own 
expense. 

3

 

Technical Data 

(typical at 20°C, after 5min., +5V supply)

 

 

Analog Inputs 

Channels // Sampling rate 

16 single-ended // up to 10 values/second per channel can be sampled (depending on software and PC)  

Surge protection: 

max. 

±

12V (when turned on), max. 

±

7V (when turned off), max. 

±

20mA in total of all input channels! 

Input resistance // Input capacity: 

1M

W

 (with PC turned off: 1k

W

) // 5pF 

Zero shift // Gain drop: 

±

50ppm/°C // 

±

50ppm/°C 

 

Measurement range 

Resolution 

abs. accuracy 

typ. noise 

Accuracy: 

±

5V 

12 Bit (2,5mV) 

±

5mV 

±

1 LSB 

 

The values for accuracy always relate to the respective measuring range. Errors might add at worst. 

 

Analog Output 

Voltage range // Output current: 

1 voltage output with 

±

5V // 1mA max. 

Resolution // Accuracy: 

12 bit // typ. 

±

4 LSB, max. 

±

20 LSB 

Zero shift // Gain drop: 

±

50ppm/°C // 

±

50ppm/°C 

 

Digital Inputs/Outputs 

Channels // Level: 

16 digital lines // CMOS/TTL compatible (low: 0V..0.7V; high: 3V..5V) 

Input resistance: 

min. 1M

W

 (with PC turned off: 1k

W

Current pick-up per output pin: 

25 mA per pin; 50 mA per pin 

Surge protection: 

max. 

±

5.5V, protected with 33

W

 

 

General Data 

Power supply: 

+4.5V..+5.5V from USB connection to the PC, max. 100mA 

USB interface: 

USB 2.0 compatible (full speed) 

Connections ( digital): 

2x40way pin connectors (RM2,54) 

CE standards: 

EN61000-6-1, EN61000-6-3, EN61010-1; for decl. of conformity (PDF) visit www.bmcm.de 

ElektroG // ear registration: 

RoHS and WEEE compliant // WEEE Reg.-No. DE75472248 

Max. permissible potentials: 

60V DC acc. to VDE

, max. 1kV ESD on open lines 

Temperature ranges: 

-25°C..+70°C 

Relative humidity: 

0-90% (not condensing) 

Dimensions: 

83 x 68x x13 mm3 

Delivery: 

circuit board 

Available accessories (optional): 

USB cable 

Warranty: 

2 years from date of purchase at bmcm, claims for damages resulting from improper use excluded 

 

Software 

Software free of charge download: 

LIBAD4 SDK for C/C++ programming on Windows® 8/10;  

trial version of the measuring software NextView® to test and operate the hardware 

NextView (optional): 

professional software (versions: Professional, Lite) for the acquisition and analysis of measurement data on 

Windows®8/10 

 

Manufacturer: BMC Messsysteme GmbH. Subject to change due to technical improvements. Errors and printing errors excepted. Rev. 1.1   04/29/2020 

Содержание USB-AD-OEM

Страница 1: ...l In Outputs Digital states can be recorded or controlled in 16 digital inputs and outputs The direction of the digital lines can be selected in groups of 8 Plug Play The connection to the PC happens...

Страница 2: ...through the USB connection 3a Step Measuring with NextView To be able to use your measurement system with NextView you just need to download and install the latest version of NextView on www nextview...

Страница 3: ...analog inputs with a measurement range of 5V and an analog output in the range of 5V Signals are connected via a 40 way pin connector The maximum potentials versus ground must not exceed 7V In the ev...

Страница 4: ...Vext 19 DGND 20 DGND 21 31 32 Vusb 33 34 D 35 36 D 37 38 DGND 39 40 The lines B1 B8 are set as output and A1 A8 as input in the default state The digital in and outputs are protected with 33W resistor...

Страница 5: ...and operation The board is equipped with four holes in the corners It can be fastened in a housing via bolts The hole spacing corresponds to the position of common HDD SSD 2 5 mounting holes M3 Conne...

Страница 6: ...make sure to use a push button with debounce protection because otherwise several pulses might be recorded The 3 9kW pull down resistor is optional in order to create a defined low signal even with lo...

Страница 7: ...ve the total current listed in the technical data see chapter 3 4 2 2 Connecting a Relay A connected relay is ideal to switch higher currents Since the field coil of the relay requires a higher curren...

Страница 8: ...to 10 values second per channel can be sampled depending on software and PC Surge protection max 12V when turned on max 7V when turned off max 20mA in total of all input channels Input resistance Inp...

Отзывы: