2-3. UPS Positioning
The UPS should be installed in the environment with free ventilation, less dust, optimum ambient
temperature and humidity.
The recommended ambient temperature is 20°C~25°C with 50% humidity.
Ambient temperature: 0°C~+40°C
Storage temperature: -15ºC ~ 60ºC
Relative humidity: 0 ~ 95%
Altitude: If the UPS is installed within 1000m, the UPS power will not be derated. When the height is
over 1000m, the output power will be derated by following the table.
Altitude(m)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Coefficient
100%
95%
91%
86%
82%
78%
74%
70%
67%
Vertical: No vibration and the degree of deviation from vertical shouldn’t be more than 5°.
Space: It’s requested to have a clearance of approx. 50 cm to the front and back of the unit and approx.
50 cm to the side.
Caution!
It’s NOT allow to have flammable, explosive or corrosive gas or liquid in installation
environment. It is forbidden to install in a metal conductive dust environment.