background image

F-2000

Page 12

7.2.2 What Features Are Available On The MODEL RT?

!

Press

to toggle between RATE and TOTAL display modes. The icon 

will light to indicate the active mode.

!

Press and hold

for at least 1.25 seconds to enter the programming mode. 

Allow twenty seconds to pass so the display will switch back to the readout 

mode. See section 7.1.

!

While the TOTAL mode is displayed, press

to reset the total amount to 

ENTER

ENTER

TOTAL

CLEAR

0

              

RATE TOTAL  

00000

              

RATE

0

              

TOTAL  

7.2.3 How Do I Determine My Calibration Numbers?

When ordered as a complete system, the F-2000 MODEL RT is factory programmed to the flow range you specified when 
you placed your order. See section 4.0 for various flow ranges.

Note:

 The F-2000 model AO and PC functions will 

always 

require field programming. 

All

 F-2000 models will require field 

programming when components are purchased separately. See section 7.2 and 7.3.

The following screens are used to input the calibration constants and to turn on or off the various features of the MODEL 
RT. The MODEL RT has six different input screens. They are listed in the table below.

  Screen No.

  Programming Functions

  RATE

1

  RATE

2

  RATE

3

  TOTAL

1

  TOTAL

2

  TOTAL

3

  Input flow Rate Scale Factor - (S )

r

  Input flow rate display Decimal Point Factory - (D )

r

  Toggle Battery Saving mode - on / off (factory default: off)

  Input flow Total Scale Factor - (S )

t

  Input total flow display Decimal Point Factor - (D )

t

  Toggle front panel Clear Total button - on (enabled) / off (disabled) -- (factory default: off)

Before programming the unit, the following calibration constants must be determined. Remember, when 

purchased as a complete system, the model RT is pre-programmed at the factory. No further programming is 

necessary.

F-2000

Page 13

Step 1

Where would you like your displayed flow rate decimal point located?

Desired Location

=

D  (Decimal Rate Factor)    

Note: 

Four decimal places maximum.

r

XXXXX

= 1

XXXX.X

= 10

XXX.XX

= 100

XX.XXX

= 1000

X.XXXX

10000

Enter your D  here.

 

 

 

r

Step 2

What time factor would you like to use in your measurement?

Example:

Per Minute =

60  seconds

Per Hour

=

3600  seconds

Per Day

=

86400  seconds

Fill in the amount of seconds you desire here.

 

 

Step 3

To determine your flow rate K-Factor, the following information is needed.

a. What size pipe you are going to install this meter on?

   

 

 

inch pipe

b. What schedule pipe are you using?  

 

 Sch 40   or  

  

Sch 80   or  

 

 Inline

c. What is your flow range?

    

 

 

Low Flow   or

    

 

 

Standard Flow (refer to pages 16 & 17)

d. Using the data you specified above, locate your K-Factor from the correct table. Pages 16 & 17.

e. What is your K-Factor?

   

 

f. If you are going to be using gallons as your unit of measure, you can go directly to Step 4.

g. To convert K-Factor to other units of measure, use the following formulas:

Ounces

=

K-factor ÷ 128

Liters

=

K-factor ÷ 3.785

Cubic Meters

=

K-factor ÷ 0.003785

 

Example:

To convert 2” schedule 80 gallons K-factor to 
liters, you will use the following formula:

Note: Locate your K-factor off the table on pages 16 & 17..

58.82 (K-factor)

3.785

=   15.54

Your new liters K-factor is  15.54

Write your new K-Factor number here.

 

 

Содержание F-2000

Страница 1: ...NSTRUCTION MANUAL 5300 Business Drive Huntington Beach CA 92649 USA Phone 714 893 8529 FAX 714 894 9492 E mail sales blue white com or techsupport blue white com Website www blue white com Blue White...

Страница 2: ...2 Optional Circuit Board Installation 8 6 3 Model RT Circuit Board Wiring 9 6 4 Model FHXX and FCXX Sensor Wiring 10 7 0 Operation 11 7 1 Theory of operation 11 7 2 Model RT Operation 11 7 2 1 Model R...

Страница 3: ...oad 8 amps 115 VAC 220 VAC 230 VAC 7 amps 30 VDC resistive load Maximum fluid debris size 0 020 diameter Model RT Measure and display the rate of flow Measure and display the total flow Model AO Measu...

Страница 4: ...60 C 130 F 54 4 C 120 F 48 9 C 110 F 43 3 C 3 2 Dimensional Drawing Fig 1 3 25 in 82 55 mm 4 00 in 101 6 mm 4 00 in F 2000 F 2000 BLUE WHITE INDUSTRIES Flow Monitoring System FlowMonitoringSystem TOTA...

Страница 5: ...IES Low Flow Range 2 Min Max 500 5 000 Pipe Size 3 8 INLINE 1 2 INLINE 3 4 INLINE 1 0 INLINE 1 1 2 INLINE 2 0 INLINE GPM 2 20 0 200 0 400 4 000 800 8 000 2 00 20 00 10 0 100 0 15 0 150 0 GPH 2 30 00 3...

Страница 6: ...h Screws Step 1 Remove Two Screws Fig 6 Angle Mount on Horizontal Pipe 45 Acceptable 45 Acceptable Recommended Vertical Fig 7 Fig 9 Fig 8 in 032 000 3 622 mm 80 00 92 0 F 2 0 0 0 P A N E L B R A C K E...

Страница 7: ...g Information Fig 10 Fig 11 Kit Number 71000 301 71000 302 71000 303 71000 304 71000 305 71000 306 71000 307 Decription Wall Mount Kit Pipe Mount Kit for 1 1 2 pipe Pipe Mount Kit for 2 pipe Pipe Moun...

Страница 8: ...id tight connector 3 4 knock out the acceptable cable diameter is between 200 394 in 5 1 10 0 mm For the small liquid tight connector 1 2 knock out the acceptable cable diameter is between 118 255 in...

Страница 9: ...al Function 6 2 3 1 3 2 7 4 Supply power input AC coil sensor input Hall Effect sensor input Open connector pulse output from sensor Positive power input red wire from battery pack or black with strip...

Страница 10: ...ing RED Input Supply Voltage 6 to 24 Vdc BARE Signal Output square wave BLACK Ground RED Signal Output Sine wave BLACK Ground Model FHXX Model FCXX Note Output type current sinking type hall effect se...

Страница 11: ...bottom of the LCD display indicating the mode being displayed The model PC is described in a separate instruction manual The MODEL AO includes all of the features of the MODELRT as well as a 4 20mA o...

Страница 12: ...require field programming All F 2000 models will require field programming when components are purchased separately See section 7 2 and 7 3 The following screens are used to input the calibration con...

Страница 13: ...r on inch pipe b What schedule pipe are you using Sch 40 or Sch 80 or Inline c What is your flow range Low Flow or Standard Flow refer to pages 16 17 d Using the data you specified above locate your K...

Страница 14: ...maximum t XXXXX 1 XXXX X 10 XXX XX 100 XX XXX 1000 X XXXX 10000 Enter your D here t Step 6 Determine your Total K factor Your Total K factor and Flow Rate K factor are the same if the same units i e...

Страница 15: ...hen finished press This will move you to the RATE 2 screen Press once to see the decimal point appear Press repeatedly until the decimal point is located in the desired location Then press to move you...

Страница 16: ...0 90 110 110 81 4 76 6 99 4 93 6 230 2300 230 2300 350 3500 350 3500 5 294 5 944 2 942 3 107 11 3335 10 0944 20 3969 19 3133 00000 00000 00000 00000 00 1889 00 1682 00 3399 00 3219 00000 00000 00000 0...

Страница 17: ...095 4 4757 6 4451 0000 0 0000 0 00 0075 00 0107 00000 00000 1 1 2 Saddle Models Pipe insertion connection Standard Flow Range GPM gallons per minute RATE 1 RATE 2 TOTAL 1 TOTAL 2 80 40 40 80 1 5 1 5 2...

Страница 18: ...RATE SETPOINT 3 ENTER 00000 RATE SETPOINT 4 ENTER 000 RATE SETPOINT 5 ENTER Setpoint Rate 2 High Alarm Release Setpoint Rate 3 Low Alarm Trigger Setpoint Rate 4 Low Alarm Release Setpoint Rate 5 Alarm...

Страница 19: ...the batteries open the front panel of the enclosure by removing the four Phillips screws After replacing the batteries be sure the foam insert is in place before closing the front panel Test the elect...

Страница 20: ...00 AO 1 14 71000 316 Kit Circuitry model F 2000 PC 1 15 90011 155 Screw 6 32 x 31 PH pan SS 4 16 76001 149 Enclosure F 2000 sensor mount 1 76001 150 Enclosure F 2000 panel mount 1 17 90006 593 Gasket...

Страница 21: ...2 23 23 26 26 25 25 24 24 27 27 28 28 32 32 31 31 30 30 29 29 11 11 15 15 5 5 5 5 5 5 20 20 22 22 F 2000 F 2 0 0 0 BLUE WHITE INDUSTRIES Flow Monitoring System FlowMonitoringSystem TOTA L CLEAR CLEAR...

Страница 22: ...tening use of non recommended chemicals use of non recommended pipe dopes or adhesives excessive heat or pressure or allowing the meter to support the weight of related piping Flowmeters are repaired...

Отзывы: