5. PROGRAMMING VARIABLE TIME & SPEED OPERATIONS
F
ollow the programming steps in this section
carefully.
Take your time so you complete the
programming successfully the first time. It is helpful to have a second person to read the
programming steps from the manual as you enter the values with the operation buttons.
A. Operating modes:
These pumps have two operation modes: Manual and Automatic. You can switch
back and forth for your preferred operating mode. To switch between modes, press the
“UP” and “DOWN” buttons at the same time.
1.0) MANUAL OPERATING MODE:
(Image #1)
*In Manual Mode, the pump runs at the constant speed set by the user. (See Image #1)
1.1)
Manual mode has four default speeds : “LOW”, “MEDIUM”, “HIGH”, “FULL”
1.2)
The default speeds cannot be changed. However, you can adjust to a temporary pump
speed within a default setting with the “UP” or “DOWN” buttons.
1.3)
Once you have the temporary speed set, press the “SET” button to adjust to
next default speed.
1.4)
In Manual mode, if you turn off the pump, the current speed can be auto-saved when you
use the pump next time.
2.0) AUTOMATIC OPERATING MODE:
• To start Automatic Mode Programing
press “SET” once (See Image #2).
- Automatic Mode will not function until Current Time and Times & Speeds Parameters
are programmed. Follow the instructions below to program Current Time and the Times & Speeds
Parameters for each segment.
(Image #2)
NOTICE
Speed Table
Low
Medium
High
Full
Lowest Speed
1150
1150
1150
1150
Highest Speed
3450
3450
3450
3450
Default Speed
1150
1700
2800
3450