Dynamic Power Factor Correction 
Thyristor Module TSM-AT

 

 
 

General: 

 
Conventional  systems  for  power  factor  correction  are  used  to  optimize  the  power  factor  and 
reduce the level of harmonics in the net. The usage of new technologies in modern industry has 
negative impacts on electrical power quality of the main supply networks, eg. frequent high load 
fluctuations  and  harmonic  oscillation.  Excessive  currents,  increased  losses  and  flickering  will  not 
only  influence  the  supply  capacity  but  will  also  have  a  significant  impact  on  the  operation  of 
sensitive electronic devices. The solution for this are dynamic power factor correction systems.  
With  the  TSM-AT  module  we  provide  the  main  component  –  „electronic  switch“  –  for  dynamic 
power  factor  correction.  The  TSM-AT  is  a  fast  electronically  controlled,  self-observing

 

thyristor 

switch for capacitive loads up to 100 kVAr, which is capable to switch PFC capacitors within a few 
milliseconds as often as required. 

 
 

Features: 

 

-

 

Real 3-phase switching 
(usage only with single-phase capacitors 
L-N) 

-

 

Output up to 120 kVAr at 690 V 

-

 

Usage for PFC-systems with and without 
reactors (programmable) 

-

 

Connected load (output) programmable 

-

 

Easy  programming  for  the  individual 
application 

via 

multi-lingual 

plain 

language display 

-

 

Indication  of  all  relevant  parameters  of 
the grid  
(voltage, current, temperature...) 

-

 

Alarm output and error message storage 

.

 

 

 

Technical Data 

 

Voltage  

 

max. 690V ( 3 x 400V L-N ) 

 
Max

.

 power 

 

up to 120 kVAr at 690 V 

 

 

 

up to 100 kVAr at 525 V 

 
Parameter setting 

nominal voltage, degree of detuning, overcurrent, alarm temperature, 

via display 

  

frequency, error message storage, delay time during cascading 

  
Control features 

permanent monitoring of net voltage, phasing, capacitor current, 

 

 

 

module temperature. Malfunction shown in plain language and evaluated;  

 

 

 

former errors are stored in an error message storage 

 
Display 

3-phase indication of net voltage and capacitor current 

 

temperature values and all parameters programmed can be retrieved 

 
Controlling 

10-24 VDC , internally DC-insulated; manual operation possible 

 
Power circuit 

connection: three-pole via clamp (25qmm) 

 
Losses 

Pv(in W)= 3.0 * I (in A) at 690V / 100 kVAr approx. 240W) 

  
Fuses   

 

electronic fuse „superfast“ 160 A (NH00) 

 
Dimensions 

 

300 x 300 x 200 mm (w x h x d) 

 
 

Содержание TSM-AT

Страница 1: ...ase capacitors L N Output up to 120 kVAr at 690 V Usage for PFC systems with and without reactors programmable Connected load output programmable Easy programming for the individual application via multi lingual plain language display Indication of all relevant parameters of the grid voltage current temperature Alarm output and error message storage Technical Data Voltage max 690V 3 x 400V L N Max...

Страница 2: ...tor which is connected to terminals X3 1 and 2 For cascading of several modules for increase of the kVAr output parallel connection is possible For additional modules programming of delay time is possible Pic 1 C3 C2 C1 3x4AT Control Input 1 activation signal 12V 2 activation signal 12V 3 and 4 alarm output zero potential max 250V 6A 5 and 6 n c Ausschnitt 65x20 mm Thy ristor Power Switch for capa...

Страница 3: ...ation During automatic operation the module can be turned ON and OFF via arrow buttons manually manual operation The operation mode is indicated in the display AUTO HAND The ON mode of the module is indicated in the display by a capacitor symbol Operating diagram Programming E xpert mode Fault memory 1 PASSWORD 0 2 BASIC SETTINGS NEW NO 3 PROGRAM LOCK NO 4 SWITCHING ON DELAY 0 PERIODS 1 VOLTAGE 40...

Страница 4: ...threshold value the module will reconnect Errors are indicated via relay contact and visualized via Display All error messages are summarized as a centralized error message and the output occurs via a relay contact In the programming menu it can be selected if this output should be stored or whether it should only be displayed during the malfunction NOTE THE FOLLOWING INSTRUCTIONS The power capaci...

Отзывы: