47
Configuration and adjustment variables
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
11960
2059 / 3D
rSL
RW0
Restart error threshold ("wake-up" threshold)
Unit: 0.1
Factory setting: 0
Adjustment range: 0 to 1000
If the "PI" and "Low speed operating time"(tLS) (see page
) functions are configured at the
same time, the PI regulator may attempt to set a speed lower than LSP.
This results in unsatisfactory operation which consists of starting, operating at low speed then
stopping, and so on…
Parameter rSL (restart error threshold) can be used to set a minimum PI error threshold for
restarting after a stop at prolonged LSP.
The function is inactive if tLS = 0.
11908
2059 / 9
PII
R/WS
Internal PI reference enabled
Factory setting: 0
0 = "nO": The PI regulator reference is Fr1, except for UPdH and UPdt (+/- speed cannot be
used as the PI regulator reference).
1 = "YES": The PI regulator reference is internal via parameter rPI.
11920
2059 / 15
rPI
R/W
Internal PI reference
Unit: 0.1%
Factory setting: 0
Adjustment range: 0 to 1000
10001
2046 / 2
bLC
R/WS
Brake control configuration
Factory setting: 0
Function active only if LAC = L2 or L3 (page
).
0 = "nO": Not assigned
2 = "r2": Relay R2
64 = "dO": Logic output AOC
If bLC is assigned, parameters FLr (page
) are forced to nO, and parameter
OPL (page
) is forced to YES.
bLC is forced to nO if OPL = OAC (page
).
Note This function may be incompatible with other functions (see page
).
10002
2046 / 3
brL
R/WS
Brake release frequency
Unit: 0.1 Hz
Factory setting: According to drive rating
Adjustment range: 0 to 100
10006
2046 / 7
Ibr
R/WS
Motor current threshold for brake release
Unit: 0.1 A
Factory setting: According to drive rating
Adjustment range: 0 to 1.36 In (1)
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the
drive rating plate.
10004
2046 / 5
brt
R/WS
Brake release time
Unit: 0.01 s
Factory setting: 50
Adjustment range: 0 to 500
10003
2046 / 4
bEn
R/WS
Brake engage frequency threshold
Unit: 0.1 Hz
Factory setting: 65535
Adjustment range: 0 to LSP
65535 = "nO": Not set
0 to LSP: Adjustment range in Hz
If bLC is assigned and bEn still equals nO, the drive will lock on a bLF detected fault on the first
run command.
10005
2046 / 6
bEt
R/WS
Brake engage time
Unit: 0.01 s
Factory setting: 50
Adjustment range: 0 to 500
10007
2046 / 8
bIP
R/WS
Brake release pulse
Factory setting: 0
0 = "nO": While the brake is releasing, the motor torque direction corresponds to the direction
of rotation commanded.
1 = "YES": While the brake is releasing, the motor torque direction is forward, regardless of the
direction of operation commanded.
Note: Check that the motor torque direction for "Forward" control corresponds to the upward
direction of the load. If necessary, reverse two motor phases.