28
Configuration and adjustment variables
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
11302
2053 / 3
JF2
R/W
2
nd
skip frequency
Unit: 0.1 Hz
Factory setting: 0
Adjustment range: 0 to 5000
Used to avoid prolonged operation at a frequency range of ± 1 Hz around JF2. This function
helps to prevent a speed which leads to resonance. Setting the function to 0 renders it inactive.
9201
203E / 2
CLI
R/W
Current limit
Unit: 0.1 A
Factory setting: 1.5 In (1)
Adjustment range: 0.25 to 1.5 In (1)
Used to limit the torque and the temperature rise of the motor.
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the
drive rating plate.
11701
2057 / 2
tLS
R/W
Low speed operating time
Unit: 0.1 s
Factory setting: 0 (no time limit)
Adjustment range: 0 to 9999
Following operation at LSP for a defined period, a motor stop is requested automatically. The
motor restarts if the frequency reference is greater than LSP and if a run command is still
present.
Note, value 0 corresponds to an unlimited time.
11003
2050 / 4
Ftd
R/WS
Motor frequency threshold
Unit: 0.1 Hz
Factory setting: bFr
Adjustment range: 0 to 5000
Motor frequency threshold above which the relay contact (R1 or R2 = FtA) closes or output
AOV = 10 V (dO = StA)
11002
2050 / 3
ttd
R/WS
Motor thermal state threshold
Unit: 1%
Factory setting: 100
Adjustment range: 0 to 118
Motor thermal state threshold above which the relay contact (R1 or R2 = tSA) closes or output
AOV = 10 V (dO = tSA)
11001
2050 / 2
Ctd
R/WS
Motor current threshold
Unit: 0.1 A
Factory setting: In (1)
Adjustment range: 0 to 1.5 In (1)
Motor current threshold above which the relay contact (R1 or R2 = CtA) closes or output AOV =
10 V (dO = CtA)
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the
drive rating plate.
12001
205A / 2
SdS
R/W
USPL/USPH scale factor
(USPL/USPH = rFr x SdS) See USPL/USPH page
Unit: 0.1
Factory setting: 300
Adjustment range: 1 to 2000
This parameter also affects the display parameter SPd1/SPd2/SPd3 in the SUP- menu
(See Programming Manual)
3015
2000 / 10
bFr
R/WS
Standard motor frequency
Factory setting: 0
0 = "50"
1 = "60"
50 Hz: IEC
60 Hz: NEMA
This parameter modifies the presets of the following parameters: HSP page
, FrS
9601
2042 / 2
UnS
R/WS
Nominal motor voltage given on the rating plate
Unit: 1 V
Factory setting: According to drive rating
Adjustment range according to drive rating:
ER23-K: 100 to 240 V
ER23
-.../
3K: 100 to 240 V
ER23
-.../
4K: 100 to 500 V
ER23
-.../
6K: 100 to 600 V