Blaze King
,
Royal Guardian,
Model RGT-3001
OWNER'S INSTALLATION AND OPERATION MANUAL
Page 19
Date Printed: Wednesday, November 07, 2012
OM-RGT.PUB
Version 1.03
REMEMBER:
Follow the manufacturer's installation instructions and maintain the manufacturer's
specified clearance distances.Install an attic insulation shield to maintain the specified clearance to
insulation. Insulation in this air space will cause a heat buildup which may ignite the ceiling joists. This
method of installation requires at a minimum a wall pass through device, a wall support package and
insulated "T" section and roof flashing.
INSTALLATION OPTIONS
Residential
1. Standard Clearance, parallel with wall, using ceiling exit.
See Page 21
2. Standard Clearance, corner installation, using ceiling exit,
See Page 24
3. Standard Clearance, parallel with wall, using wall exit.
See Page 22
4. Standard Clearance, corner installation, using wall exit.
See Page 23
5.
Reduced
Clearance,
wall
exit.
See
Page
22
6.
Reduced
Clearance,
ceiling
exit.
See
Page
21
7.
Alcove
Installation.
See
Page
24
Mobile Home (all ceiling exit)
1.
Parallel
Installation.
See
Page
24
2.
Corner
Installation.
See
Page
24
3.
Alcove
Installation.
See
Page
24
CLEARANCES
INST
CLEARANCE ILLUSTRATIONS
Fig.
*See Ref #
Above
A
B
C
D
Pg
RESIDENTIAL INSTALLATIONS
Parallel
23
1
16”
10”
25.5”
16”
19
Corner
21
1
12”
--
21.5”
--
19
Reduced Side Clearance
23
2
13”
10”
22.5”
16”
19
Reduced Corner Clearance
21
2
8”
--
17.5”
--
19
Reduced Back Clearance
23
3
16”
6”
25.5”
12”
22
Alcove
22
3
16”
6”
25.5”
12”
22
Wall Exit, Parallel
24 & 25
4
14”
10”
23.5”
16”
20,21
Wall Exit, Corner
24 & 26
4
8”
--
17.5”
--
20,21
MOBILE HOME INSTALLATIONS
Parallel
23
5
16”
6”
25.5”
12”
22
Corner
21
5
8”
--
17.5”
--
22
Alcove
22
5
18”
8”
27.5”
14”
22
ALCOVE REQUIREMENTS
Minimum Height
64"
Minimum Width
57"
Maximum Depth
30"
For wall exit, minimum clearance from horizontal pipe to ceiling is 18".
CLEARANCES TO COMBUSTIBLE SURFACES
..............................................................................................................................................................................................................................................................
WARNING
FAILURE TO ALLOW THE REQUIRED CLEARANCES TO COMBUSTIBLE MATERIALS OR TO
PROVIDE ADEQUATE FLOOR PROTECTION CAN CAUSE A HOUSE FIRE. SUCH A FIRE CAN
RESULT IN DAMAGE TO PROPERTY AND SERIOUS INJURY OR DEATH.
..............................................................................................................................................................................................................................................................
1. TABLE #1
MINIMUM CLEARANCES TO COMBUSTIBLE SURFACES
(All Dimensions are in Inches)
* These numbers correspond with the table below.