Service side change is shown by the example of the KOMFORT Ultra S 250-H/E air handling unit.
The procedure of the service side changing for KOMFORT Ultra L 250-H/E is carried out in the same manner.
CONDENSATE DRAINAGE SYSTEM CONNECTION (ONLY FOR THE KOMFORT ULTRA S/L 250-H MODEL)
The KOMFORT Ultra S/L 250-E units are equipped with an enthalpy heat exchanger and don’t require condensate drainage.
The hole for the drain pipe is at the bottom of the unit. Remove the plug from the hole, open the service panel and install the drain pipe from
the delivery set into the hole, then connect the drain pipe to the sewage system using the U-trap kit (available upon separate order). The pipe
slope downwards must be at least 3°.
Drain
pipe
Drain
hose
min 3
°
Sewage
system
Sewage pipe
Ø
32 mm
U-trap