INSTALLATION AND SET-UP
FS2 HUMIDITY SENSOR INSTALLATION AND CONNECTION (FOR UNITS WITH S14 AND S21 CONTROL)
The FS2 humidity sensor is not included in the delivery set and is available as a specially ordered accessory.
The humidity sensor must be installed prior to the unit mounting.
Install the humidity sensor through the extract spigot into the mount on the extract air duct panel. After that connect the humidity
sensor plug to the respective socket on the control unit, refer to the External wiring diagram.
UNIT INSTALLATION
To attain the best performance of the unit and to minimize turbulence-induced air pressure losses, connect the straight air duct section
to the spigots while installing.
Minimum straight air duct length:
• equal to 1 air duct diameter on the intake side
• equal to 3 air duct diameters on outlet side
READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.
BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES,
READ THE RELEVANT USER MANUALS
The air ducts must be slipped over the unit flanges until tight. Flexible air ducts must be rigidly fixed with a metal worm clamp.
www.blaubergventilatoren.de
KOMFOrt EC S5(B) 270(-E)
9