17
• The unit is rated for connection to 3~400 V/50 (60) Hz power mains.
• The connection must be made using durable, insulated and heat-resistant conductors (cables, wires). The actual wire cross section
selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation,
length and installation method.
• The external power input must be equipped with a automatic circuit breaker built into the stationary wiring to open the circuit in the
event of overload or short-circuit. The position of the external circuit breaker must ensure free access for quick unit power-off. The
automatic circuit breaker nominal current must exceed the ventilator current consumption, refer to the Technical data section. The
recommended trip current of the circuit breaker is the next current in the standard trip current row following the maximum current of
the connected unit. The automatic circuit breaker is not included in the delivery set and can be ordered separately.
ACCESS TO THE CONTROL UNIT
EXTERNAL WIRING DIAGRAM
L1
L1
N
N
L2
L2
L3
L3
PE
X1
X3
~400 V
C
4
C
2
NO
3
NC
1
+24V
8
A
6
B
7
GND
5
+24V
A
B
GND
10
9
1
2
Boost*
P1*
1
2
PK1*
CCU*
Designation
Unit name
Cable type
Maximum
cable length
Note
CCU*
Compressor-condenser unit
2x0.75 mm2
20 m
3 A, 30 DC/~250 AC
PK1*
Contact from a fire alarm panel
2x0.75 mm2
20 m
Remove the jumper when connecting
P1*
Control panel S22; S25
4x0.25 mm2
10 m
Boost*
Contact on/off, Boost mode
*Additionally connected devices are not included in the delivery set and should be purchased separately.
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER’S LABEL.
Power on/off Setup mode
CONNECTION TO POWER MAINS