UNIT MOUNTING
To attain the best performance of the unit and to minimise turbulence-induced air pressure losses, connect the straight air duct section
to the spigots on both sides of the unit while mounting.
Minimum straight air duct length:
• equal to 1 air duct diameter on intake side
• equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects. To prevent uncontrollable access to
the fans, the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 12.5 mm.
While installing the unit ensure convenient access for subsequent maintenance and repair.
The unit must be mounted on a plane wall. Mounting of the unit to an uneven surface can lead to the unit casing distortion and
operation disturbance.
Unit wall mounting
Unit floor mounting
Fasteners for wall mounting are not included in delivery and must
be ordered separately. While choosing fasteners consider the
material of the mounting surface as well as the weigh of the unit,
refer to the Technical Data section. Fasteners for unit mounting
must be selected by the Customer Service technician. Fix the wall
bracket on the required height and hang the unit on it.
Install the unit on the pre-mounted floor supports, minimum 150
mm height, to ensure sufficient access for the drain pipe connection
to the U-trap and for condensate drain system mounting.
min 150 mm
www.blaubergventilatoren.de
KOMFOrt EC S(1/2)(B)(-E)
12
Содержание 4058448021602
Страница 20: ...www blaubergventilatoren de KOMFORT EC S 1 2 B E 20 ...
Страница 21: ...www blaubergventilatoren de KOMFORT EC S 1 2 B E 21 ...
Страница 22: ...www blaubergventilatoren de KOMFORT EC S 1 2 B E 22 ...
Страница 24: ...www blaubergventilatoren de B106 1EN 09 ...