VENTO Ergo A50/50-1 Pro
The jumper between the contacts 1 and 2 or 2 and 3 of CN7 socket
connector determines the air flow direction in Ventilation mode:
• If the jumper connects the contacts 1 and 2, air is extracted from the
room in Ventilation mode (factory setting).
• If the jumper connects the contacts 2 and 3, air is supplied to the room
in Ventilation mode.
The jumper position at each connected in series unit determines a
rotation direction in the Ventilation mode and an operating phase in the Heat
Recovery mode. I.e. if the jumper at the first unit connects the contacts 2 and
3 and the jumper at the second unit connects the contacts 1 and 2, the units
operate in opposite directions in the Heat Recovery mode.
L
N
G
D
+
+
N
L
N
G
D
+
+
N
control unit with
jumper contacts
TB2
CN7
1
2
3
4
5
6
Output
L
G
-
D
N
Input
L
G
-
D
N
Output
L
G
-
D
N
Input
L
G
-
D
N
Output
L
G
-
D
N
Input
L
G
-
D
N
1~100-230 V
50-60 Hz
1~100-230 V
50-60 Hz
Unit №10
Connection in series of above 10 units
Unit №11
Unit №1
TO THE NEXT
UNIT
2. Connection in series of above 10 units.
In case of connection above 10 units power is supplied to the 11th unit (L
and N terminals) not from the previous unit but from power mains.
The control signals G and D from the 10th unit are transferred through
the cable 2 x 0.5 mm
2
.
TThe units no. 12…20 are connected to the unit no. 11 in the same way as
the units no. 2…10 are connected to the first unit. All the connected units are
controlled with the unit no. 1.
All the connected in series units must be grounded!
Fig. 18
Fig. 19. Connection in series for more than 10 units
Fig. 20. Control switches on the ventilation unit
Fig. 21. Remote controller
The unit is operated with the switches on the unit casing or with the
remote controller.
The unit control with the operation switches on the unit casing has
limited functionality:
1. Activate the second and the third speed only;
2. Set three of four ventilation modes.
The remote controller has a wider control functionality.
Humidity control is possible from the remote controller only!
Speed switch
Ventilation mode
switch
UNIT CONTROL
Unit ON/OFF
Night mode
Heat Recovery
Speed setting (3-2-1)
Passive air supply
Ventilation1
Air supply at set speed2
Humidity setting