The jumper between the contacts 1 and 2 or 2 and 3 of CN7 socket 

connector determines the air flow direction in Ventilation mode:

•  If the jumper connects the contacts 1 and 2, air is extracted from the 

room in Ventilation mode (factory setting). 

•  If the jumper connects the contacts 2 and 3, air is supplied to the room 

in Ventilation mode.

The jumper position at each connected in series unit determines a 

rotation direction in the Ventilation mode and an operating phase in the Heat 

Recovery mode. I.e. if the jumper at the first unit connects the contacts 2 and 

3 and the jumper at the second unit connects the contacts 1 and 2, the units 

operate in opposite directions in the Heat Recovery mode.

L

N

G
D
+

+

N

L

N

G
D
+

+

N

control unit with 

jumper contacts

TB2

CN7

1
2
3

4
5
6

Output

L

G

-

D
N

Input

L

G

-

D
N

Output

L

G

-

D
N

Input

L

G

-

D
N

Output

L

G

-

D
N

Input

L

G

-

D
N

1~100-230 V

50-60 Hz

1~100-230 V

50-60 Hz

Unit №10

Connection in series of above 10 units

Unit №11

Unit №1

TO THE NEXT 

UNIT

2. Connection in series of above 10 units.

In case of connection above 10 units power is supplied to the 11th unit (L 

and N terminals) not from the previous unit but from power mains.

The control signals G and D from the 10th unit are transferred through 

the cable 2 x 0.5 mm

2

TThe units no. 12…20 are connected to the unit no. 11 in the same way as 

the units no. 2…10 are connected to the first unit. All the connected units are 

controlled with the unit no. 1. 

All the connected in series units must be grounded!

Fig. 18 

Fig. 19. Connection in series for more than 10 units

Fig. 20. Control switches on the ventilation unit

Fig. 21. Remote controller 

The unit is operated with  the switches on the unit casing or with the 

remote controller.

The unit control with the operation switches on the unit casing has 

limited functionality:

1. Activate the second and the third speed only;
2. Set three of four ventilation modes. 

The remote controller has a wider control functionality. 

Humidity control is possible from the remote controller only! 

Speed switch

Ventilation mode 

switch 

UNIT CONTROL

Unit ON/OFF

Night mode

Heat Recovery

Speed setting (3-2-1)

Passive air supply

Ventilation1

Air supply at set speed2

Humidity setting

Содержание Vento Expert A50-1 Pro

Страница 1: ...OPERATION MANUAL VENTO Ergo A50 Pro VENTO Ergo A50 S Pro VENTO Ergo A50 1 Pro VENTO Ergo A50 1 S Pro SINGLE ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY...

Страница 2: ...on and storage rules 3 Manufacturer s warranty 3 Design and operating logic 4 Modifications and options 5 Delivery set 5 Technical data 6 Mounting 7 Connection to power mains 10 Unit control 11 Mainte...

Страница 3: ...ion manual prior to any electric installations Connection of the unit to power mains is allowed by qualified professionals WARNING Read the operation manual prior to any electric installations Connect...

Страница 4: ...y Take steps to prevent ingress of smoke carbon monoxide and other combustion products into the room through open chimney flues or other fire protection devices Sufficient air supply must be provided...

Страница 5: ...h a motor meter with non volatile memory After 90 days non stop operation the sound signal reminds of the need to clean or replace the filters The signal is repeated every 5 minutes until the filters...

Страница 6: ...Ergo A50 1 Pro Unit with a flat front panel for 250 up to 470 mm walls VENTO Ergo A50 1 S Pro Unit with a flat front panel for 120 up to 300 mm walls DELIVERY SET Unit 1 item Mounting plate 1 item Fix...

Страница 7: ...Max air flow m3 h 13 27 51 RPM min 1 580 760 1378 Sound pressure level at 3 m distance dBA 19 22 29 Transported air temperature C from 20 up to 50 Filter extract supply G3 Heat recovery efficiency up...

Страница 8: ...the surface of the mounting plate The unit is designed for through the wall mounting in the building outer wall Mounting sequence 1 Prepare a round core hole through the outer wall The size is shown...

Страница 9: ...S Pro Mark the holes with the master plate from the delivery set Drill 40 mm deep holes for the dowel 6x40 8 Insert the dowels 6x40 from the delivery set into the holes 9 Disassemble the outer ventil...

Страница 10: ...ewallwiththescrews4x40fromthedelivery set Fig 15b models VENTO Ergo A50 S Pro and VENTO Ergo A50 1 S Pro Fix the back part of the outer ventilation hood to the wall with the screws 4x40 from the deliv...

Страница 11: ...one in the same way etc Up to 10 units may be connected in series fig 18 For electric installation use a five wire cable not included into the delivery set with the cable cross section not below 0 5 m...

Страница 12: ...THE NEXT UNIT 2 Connection in series of above 10 units In case of connection above 10 units power is supplied to the 11th unit L and N terminals not from the previous unit but from power mains The co...

Страница 13: ...Heat Recovery mode If the indoor humidity exceeds the set point the unit switches to the third speed If the humidity is within 5 the unit operates at the second speed If the indoor humidity is below...

Страница 14: ...er located after the heat exchanger Clean the filters as often as required but at least once in three months After 90 days non stop operation the sound signal reminds of the need to clean or replace t...

Страница 15: ...e troubleshoot the connection error Jammed motor soiled impeller blades Turn the unit off Troubleshoot the motor jam and the impeller clogging Clean the blades Restart the unit Automatic switch trippi...

Страница 16: ...tes relating to electromagnetic compatibility This certificate is issued following test carried out on samples of the product referred to above Approval mark Manufacturing date____________________ Com...

Страница 17: ...____________________________________ _______________________________________________________________________________________ ___________________________________________________________________________...

Страница 18: ...____________________________________ _______________________________________________________________________________________ ___________________________________________________________________________...

Страница 19: ...____________________________________ _______________________________________________________________________________________ ___________________________________________________________________________...

Страница 20: ...www blaubergventilatoren de VENTO Ergo A50 Pro v 3 6 EN...

Отзывы: