6

TECHNICAL DATA

The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to 
60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above 
the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a minimum 
(20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage electronic 
components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

TECHNICAL DATA

MODEL

KOMFORT EC DBE 2000  

KOMFORT EC DBE 3000  

Voltage [V/50 (60) Hz] 

3~ 400

Maximum fan power [W]

876

2226

Power of the integrated electric heater [W]

15000

21000

Maximum air flow [W]

15876

23226

Maximum unit current without a heater [A]

5.3

3.5

Current of the integrated electric heater [A]

21.7

30

Maximum current of the unit with an electric heater [A]

27.0

33.5

Air flow [m

3

/h]

2100

4300

Rotation speed [min

-1

]

2920

3400

Noise level, 3 m [dBA]

36

46

Transported air temperature [°C]

-25...+40

Casing material 

Aluzinc

Insulation, mineral wool [mm]

25

25

Filtering class of the extract filter

G4

Filtering class of the supply filter 

G4

Connecting air duct diameter [mm]

315

400

Weight [kg]

140

281

Heat recovery efficiency [%]

50...67

59...72

Heat exchanger type 

Cross-flow

Heat exchanger material 

Aluminium

SEC class

NRVU

NRVU

Содержание KOMFORT EC DBE 2000

Страница 1: ...Heat recovery air handling unit USER S MANUAL EN KOMFORT EC DBE 2000 KOMFORT EC DBE 3000 ...

Страница 2: ... practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country Safety requirements 3 Purpose 5 Delivery set 5 Designation key 5 Technical data 6 Design and functioning 8 Mounting and set up 9 Connection to power mains 11 Technical maintenance 12 Troub...

Страница 3: ...ications are not allowed Do not expose the unit to adverse atmospheric agents rain sun etc Transported air must not contain any dust or other solid impurities sticky substances or fibrous materials Do not use the unit in a hazardous or explosive environment containing spirits gasoline insecticides etc Do not close or block the intake or extract vents in order to ensure the efficient air flow Do no...

Страница 4: ...h as a timer or connected to a circuit that is regularly switched on and off by the utility Ensure that the unit is switched off from the supply mains before removing the guard WARNING If there are any unusual oscillating movements immediately stop using the unit and contact the manufacturer its service agent or suitably qualified persons The replacement of parts of the safety suspension system de...

Страница 5: ...e mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogenic germs THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNEC...

Страница 6: ...Class I electrical appliance Hazardous parts access and water ingress protection rating IP22 for the unit connected to the air ducts IP44 for the unit motors The unit design is constantly being improved thus some models may be slightly different from those described in this manual TECHNICAL DATA MODEL KOMFORT EC DBE 2000 KOMFORT EC DBE 3000 Voltage V 50 60 Hz 3 400 Maximum fan power W 876 2226 Pow...

Страница 7: ...2000 3000 7 OVERALL DIMENSIONS OF THE UNIT L1 ØD Ød L H H1 B B2 B3 B2 B1 B1 Dimensions mm Model Ø D В В1 В2 ВЗ Н Н1 L L1 Ø d KOMFORT EC DBE 2000 315 950 405 225 500 762 367 1400 1453 9 KOMFORT EC DBE 3000 400 1265 563 347 570 881 427 1835 1888 9 ...

Страница 8: ...and preventive maintenance and a cover enabling access to the control system components OPERATING LOGIC Extract air Supply air Intake air Exhaust air The basic unit delivery set includes a remote control panel for connection to the control system inside the unit casing The unit comprises a supply and an extract centrifugal single inlet fan with forward curved blades and maintenance free EC motors ...

Страница 9: ...he best performance of the unit and to minimise turbulence induced air pressure losses while mounting connect a straight air duct section on both sides of the unit Minimum straight air duct length equal to 1 air duct diameter on intake side equal to 3 air duct diameters on outlet side If the air ducts are not connected or the connected air ducts are too short protect the unit parts from ingress of...

Страница 10: ...n pan in the heat recovery section is equipped with two hoses for extracting the condensed fluid outside the unit Connect the pipe U trap not included in the delivery set and the sewage collection system with metal plastic or rubber connecting pipes The pipe slope downwards must be at least 3 Fill up the system with water before connecting the unit to power mains The U trap must always be filled w...

Страница 11: ...the cables through the airtight electric lead in in the unit casing and connect these to the terminal block The wiring diagram for connection of the air handling unit to power supply is on the back side of the lid CONNECTION TO POWER MAINS KOMFORT EC DBE 2000 S21 EXTERNAL WIRING DIAGRAM L2 L1 1 2 3 4 5 6 7 8 9 10 C 11 NC 12 C 13 14 15 16 17 18 19 20 21 22 23 24 25 26 NO GND 0 10 24V Gnd A B 24V NO...

Страница 12: ...C DBE 3000 S21 EXTERNAL WIRING DIAGRAM 1 2 3 4 5 6 7 8 C 9 NC 10 C 11 NO 12 GND 13 14 15 16 17 18 19 20 21 22 23 24 0 10 24V GND A B 24V NO C NO C NO C P1 1 2 PK1 CCU N L3 L2 L1 X1 SM1 SM2 U Boost CO2 1 2 Gnd 0 10V 24V Gnd 24V A B 1 2 U 1 2 P1 1 2 PK1 CCU X1 SM1 SM2 U Boost CO2 1 2 Gnd 0 10V 24V Gnd 24V A B 1 2 U 1 2 400 V 50 60 Hz Design Name Type Wire Note SМ1 Supply air damper actuator NO 2 x 0...

Страница 13: ... 3 Fan inspection once a year Even regular technical maintenance of the filters and the heat exchanger may not completely prevent dust accumulation in the fans which reduces the fan capacity and impairs supply air volume into the premises The fans must be cleaned by a service technician 4 Condensate drain maintenance 4 times a year The drain pipes may get clogged with the extracted particles Pour ...

Страница 14: ...UST BE CARRIED OUT BY QUALIFIED SPECIALISTS POSSIBLE FAULTS AND TROUBLESHOOTING Problem Possible reasons Troubleshooting The fan s does do not start up during the unit start up No power supply Make sure the unit is properly connected to power mains otherwise troubleshoot a connection error The mode is set in which the fans are off Change the operating mode using the control panel Low air flow Low ...

Страница 15: ...ontact the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s...

Страница 16: ...TION CERTIFICATE The unit _____________________________________ is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical ...

Страница 17: ...www blaubergventilatoren de KOMFORT EC DBE 2000 3000 17 ...

Страница 18: ...www blaubergventilatoren de KOMFORT EC DBE 2000 3000 18 ...

Страница 19: ...www blaubergventilatoren de KOMFORT EC DBE 2000 3000 19 ...

Страница 20: ...www blaubergventilatoren de B255 1EN 02 ...

Отзывы: