TE / TI / HSE / HSI / LSE / LSI/ IRSE / IRSI
The timer operation duration is individually
adjustable. The connected fan runs. The light indicator
blinks once in 1 second.
The timer/sensor with timer have a permanent
connected load monitoring function.
1. The light indicator glows green in rated operation
conditions when the load current up to 1.5 A.
2. The light indicator glows red when the load current
is from 1.5 up to 1.9 A. During this load current the
equipment operates in heavy duty operation mode.
The heavy-duty operation mode decreases the
service life of the timer/ sensor with timer. To avoid that,
it is recommended to decrease the connected load
down to max. 1.5 A.
3. The light indicator blinks red once in 5 seconds in
emergency operation mode, when the load current
exceeds 1.9 A. In this case the connected load is
switched off.
To restart the timer/ sensor with timer first disconnect
the device from power mains at least for 10 seconds
and connect a fan with current consumption not
exceeding 1.5 A to the device.
The timer / sensor with timer mounting procedure
depends on the casing design, either surface mounting
( TE / HSE/ LSE / IRSE models), fig. 2 or flush mounting
(TI / HSI / LSI / IRSI models), fig. 3.
Surface mounting (TE / HSE/ LSE / IRSE models):
1. Remove the decorative cover, fig. 2.1.
2. Remove 4 fixing screws from the front cover, fig. 2.2.
3. Route the cable in the wall to the installation place.
4. Lean the casing against the wall and mark the
openings for the dowels, fig. 2.3.
5. Drill the holes in the wall and install 5x25 dowels,
fig. 2.4.
6. Route the wires through the openings in the casing.
7. Fix the casing to the wall using two 3x25 screws,
fig. 2.5.
8. Strip the wires for 7-8 mm.
9. Connect the wires to the terminal blocks in compliance
with the wiring diagram, fig. 4.
10. Fix the front panel using the four screws from the
delivery set and install the decorative cover, fig. 2.6.
Flush mounting (TI / HSI / LSI / IRSI models):
1. Remove the decorative cover, fig. 3.1.
2. Remove 4 fixing screws from the front cover, fig. 3.2.
3. Prepare a recess in the wall for installation of the
casing, fig. 3.3.
4. Route the cable in the wall to the installation place.
5. Install the casing into the recess and mark the holes for
the dowels, fig. 3.4.
6. Drill holes in the wall and insert 5x25 dowels, fig. 3.5.
7. Route the wires through the electric lead-ins in the
casing.
8. Fix the casing in the wall with two 3x25 screws, fig. 3.6.
9. Strip the wires for 7-8 mm.
10. Connect the wires to the terminal blocks in
compliance with the wiring diagram, fig. 4.
11. Fix the front panel using the four screws from the
delivery set and install the decorative cover, fig. 3.7.
!
WARNING
Make sure that the device is not damaged. Do not use a damaged device!
Do not install the device on an uneven surface!
While tightening the screws avoid overtightening not to damage the device.
MOUNTING
2.1
2.2
2.3
2.4
2.5
2.6