![BLAUBERG Ventilatoren Freshbox 100 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/blauberg-ventilatoren/freshbox-100/freshbox-100_user-manual_2769971005.webp)
www.blaubergventilatoren.de
Freshbox 100
5
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to 80 %.
In order to prevent condensation on the internal walls of the units, it is necessary that the surface temperature of the casing is 2-3 °C higher
than the dew point temperature of the transported air.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
• IP22 for the unit connected to the air ducts
• IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Parameters
Fr
eshb
ox
100
Fr
eshb
ox
100
ER
V
Fr
eshb
ox
E-100
Fr
eshb
ox
E-100
ER
V
Speed
1
2
3
1
2
3
1
2
3
1
2
3
Unit voltage [V/50 (60) Hz]
1~ 230
1~ 230
1~ 230
1~ 230
Maximum fan power [W]
12
21
45
12
21
45
12
21
45
12
21
45
Preheater power [W]
-
-
700
700
Reheater power [W]
-
-
-
-
Maximum unit current (without a heater) [A]
0.4
0.4
0.4
0.4
Maximum unit current (with a heater) [A]
-
-
3.6
3.6
Maximum air capacity [m3/h]
30
60
100
30
60
100
30
60
100
30
60
100
Sound pressure level at 3 m distance [dBA]
13
27
39
13
27
39
13
27
39
13
27
39
Transported air temperature [°C]
-20...+40
-20...+40
-20...+40
-20...+40
Casing material
Painted steel
Painted steel
Painted steel
Painted steel
Insulation [mm]
10
10
10
10
Extract filter
G4
G4
G4
G4
Supply filter
G4, F8
G4, F8
G4, F8
G4, F8
Connected air duct diameter [mm]
100
100
100
100
Weight [kg]
31
31
31
31
Heat recovery efficiency [%]
96
92
87
90
86
80
96
92
87
90
86
80
Heat exchanger type
Counter-flow
Counter-flow
Enthalpy
Counter-flow
Counter-flow
Enthalpy
THE EXTRACT AIR TEMPERATURE SHOULD BE NO HIGHER THAN +40 °C AND RELATIVE
HUMIDITY SHOULD NOT EXCEED 70 % OVER THE ENTIRE TEMPERATURE RANGE.