551-A00 Page 3/21
GENERAL
IMPORTANT NOTES
1. This
Publication
is
TYPICAL ONLY
and only relates to the
specifications of the minimum equipment required to
ensure the optimum performance, maximum life and
trouble-free operation of the Ebsray RC Series Pumps and
the Pumping System in general.
2. This
Publication
does
NOT
depict:
a) Ancillary required equipment related to the fabrication,
installation and operation of the Pumpset e.g.
miscellaneous flanges, fittings etc.
b) Required equipment unrelated to the Pumpset e.g. tank
fill lines, vapor return lines, emergency shutdown
systems etc.
c)
The materials and method of fabrication and/or
installation of the tank and required sub-systems.
3.
It is the responsibility of the designer, fabricator and the
installer of each actual tank and required sub-systems to
ensure that:
a) The Ebsray specifications within this Publication and any
other relevant Ebsray documents are
STRICTLY
adhered to.
b) Any variation (including use of equipment deemed
"Equivalent") or addition to the Ebsray Specifications, as
related to the Pumpset and Pumping System in general,
meet Ebsray's minimum requirements.
c) All design, fabrication and installation of the tank and
sub-systems is
STRICTLY
in accordance with all
relevant National, State and Local Codes, Regulations,
Standards and Directives.
ABBREVIATIONS:
AFL
Automatic Fill Limiting Valve
CBS
Constant Bleed System
EFV Excess
Flow
Valve
FLA Full
Load
Amps
VRS Vapor
Removal
System
SYSTEM DESCRIPTION
Correct installation and operation is essential. Service life is
enhanced by periodic inspection and careful maintenance.
The RC Series Pumps are designed generally for installation
aboveground when connected to aboveground storage tanks.
For Underground installations – consult the factory.
BYPASS VALVE – EBSRAY MODEL RV18
The RC Series Pumps must be installed in conjunction with a
bypass valve - connected back-to-tank. The EBSRAY Model
RV18 fitted with VRS or CBS option is recommended. (Refer to
‘P&ID’ schematic for details)
The Bypass Valve plays a pivotal role in the overall LPG system.
It controls the following functions:
1.
Maintains pump system differential pressure as required for
optimum flow rates.
2.
Controls Differential Pressure to maintain pump's and/or
motor's correct operation within intended maximum
operating parameters.
3.
VRS option, when fitted, ensures rapid vapor passage for
faster pump priming before acting in its intended liquid
handling mode.