background image

5

The bypass valve and piping must be of adequate size to
accommodate the full flow from the pump when the discharge
line is closed.  Shut off valves and couplings must be provided
on both sides of the pump and bypass valve for removal and
servicing.  The pump internal relief valve is factory set at
approximately 125 psi (8.6 bar).

Refer to Blackmer Bypass Valve Installation and Maintenance
Instructions for bypass valve installation, setting and
adjustment procedures.

PUMP ROTATION 

NOTICE:

CONFIRM CORRECT PUMP ROTATION BY CHECKING
THE PUMP ROTATION ARROWS RESPECTIVE TO PUMP
DRIVER ROTATION.

TO CHANGE PUMP ROTATION 

Blackmer 

CRL4A

motor driven pump models are equipped

with a double ended rotor and shaft, enabling them to be
driven from either shaft end.  To change rotation, rotate the
pump 180 degrees so the opposite shaft becomes the driven
shaft.  The shaft protector (186) MUST be mounted over the
non-driven shaft end.

START UP PROCEDURES

NOTICE:

CONSULT THE "GENERAL PUMP TROUBLESHOOTING"
SECTION OF THIS MANUAL IF DIFFICULTIES DURING START
UP ARE EXPERIENCED.

1. Start the motor.  

2. If priming does not occur, shut off the pump and close the

pump discharge.  Open the bleed valve on the pump
discharge gauge hole until “snow” appears at the exhaust.
Close the bleed valve,  open the discharge line and start
the pump.  Repeat if necessary.

3. Check the pressure gauges to ensure the system is

operating within expected parameters.  Record the gauge
readings in the "Initial Start Up Information" section of this
manual for future reference.

4. Inspect piping, fittings, and associated system equipment

for leaks, noise, vibration and overheating.

5. Check the flow rate to ensure the pump is operating within

the expected parameters.  Record flow rate in the “Initial
Start Up” section of this manual for future reference.

6. Close the discharge valve and check the differential

pressure across the pump.  It must not exceed the
pressure setting of the external bypass valve.

7. With the discharge valve still closed, momentarily close the

manual shut-off valve in the bypass return line to check the
pump relief valve.  The pressure must be at least 25 psi
(0.7 - 1.4 bar) higher than the operating pressure or the
system pressure control valve setting.  Refer to “Relief
Valve Setting and Adjustment” section of this manual.

8. The external bypass valve must always be set at least 25

psi (1.7 bar) lower than the pump internal relief valve.
NOTE: The normal operating pressure must be at least  5 -
15 psi (0.3 -1.0 bar) less than the external bypass setting.
Pump speeds which result in higher pressures (nearing the
valve setting) forces the liquid to be recirculated, creating
excessive wear on the pump and equipment.

PRE-START UP CHECK LIST

1. Inspect complete piping system and supports to ensure

that no piping loads are being placed on the pump.

2. Install pressure gauges in the 

1

/

4

" NPT intake and

discharge ports located on the pump casing to check pump
performance after start-up. 

3. Build pressure in the pump by SLOWLY cracking the valve

in the discharge line.  When the internal pump pressure
equals tank pressure, check for system leaks.

4. Ensure all valves and fittings in piping system are in the

start-up or operating positions.

5. Jog the pump motor to verify proper pump rotation. 

INSTALLATION AND OPERATION 

CRL BASE MOUNTED MOTOR DRIVEN PUMPS

RELIEF VALVE SETTING AND ADJUSTMENT

The factory relief valve pressure setting is marked on a metal
tag attached to the valve cover.  It is recommended the relief
valve be set at least 10 - 20 psi (0.7 - 1.4 bar) higher than the
operating pressure or the system pressure control valve
setting.

Hazardous pressure
can cause personal
injury or property
damage.

I

NCORRECT SETTINGS OF THE PRESSURE

RELIEF VALVE CAN CAUSE SYSTEM

COMPONENT FAILURE, PERSONAL INJURY

AND PROPERTY DAMAGE.

OPERATING PUMP AGAINST A

CLOSED VALVE CAN CAUSE

SYSTEM COMPONENT FAILURE,

PERSONAL INJURY AND PROPERTY

DAMAGE.

Hazardous pressure
can cause personal
injury or property
damage.

Relief Valve Adjustment Procedure:

1.

To INCREASE the pressure setting

, remove the relief

valve cap (1), loosen the locknut (3), and turn the adjusting
screw (2) inward, or CLOCKWISE.

2.

To DECREASE the pressure setting

, remove the relief

valve cap (1), loosen the locknut (3), and turn the adjusting
screw (2) outward, or COUNTERCLOCKWISE. 

Refer to corresponding Blackmer pump Parts List for
relief valve spring pressure ranges.

OPERATION WITHOUT SHAFT
PROTECTOR IN PLACE CAN CAUSE
SERIOUS PERSONAL INJURY,
PROPERTY DAMAGE, OR DEATH.

Hazardous
machinery can
cause serious
personal injury.

Содержание CRL4

Страница 1: ...s which have been designed by qualified engineering personnel The system MUST conform to all applicable local and national regulations and safety standards This manual is intended to assist in the ins...

Страница 2: ...ifferential Pressure INITIAL START UP INFORMATION TECHNICAL DATA PUMP WITH WELDED CONNECTIONS NOTICE FOR PIPING CONNECTIONS REQUIRING WELDING THE PUMP S NON METALLIC O RINGS MUST BE REMOVED PRIOR TO W...

Страница 3: ...tate piping expansion and contraction expansion joints must be placed 3 feet 0 9 m from the pump intake and discharge 8 ALL piping and fittings MUST be properly supported to prevent any piping loads f...

Страница 4: ...the sheave capscrews 152C 152G the motor mounting nuts 184 and the adjusting screw locknut 183B 8 Assemble the belt guard 182 and the belt guard brace 182A to the unit base 32 9 Check the belt tension...

Страница 5: ...rating pressure or the system pressure control valve setting Refer to Relief Valve Setting and Adjustment section of this manual 8 The external bypass valve must always be set at least 25 psi 1 7 bar...

Страница 6: ...e off through universal joints When using universal joints a splined slip joint properly lubricated must be used on the connecting jack shaft to prevent end thrust on the pump shaft It is very importa...

Страница 7: ...over the non driven shaft end a Lever Operated Pull the control knob all the way out Manually check the lever under the truck to see that it is in the completely OPEN position b Discharge Pressure Op...

Страница 8: ...or the system pressure control valve setting Relief Valve Adjustment Procedure 1 To INCREASE the pressure setting remove the relief valve cap 1 loosen the locknut 3 and turn the adjusting screw 2 inw...

Страница 9: ...Slide the head 20 off the shaft The head O ring 72 disc 71 bearing 24 and mechanical seal 153 will come off with the head assembly Remove and discard the head O ring a Remove the four disc machine sc...

Страница 10: ...th the rounded edges outward and the vane relief grooves facing TOWARDS the direction of rotation Refer to Figure 7 d After the bottom vanes 14 and push rods 77 are installed carefully insert the roto...

Страница 11: ...the aligned lockwasher tang into the slot in the locknut The pump must continue to turn freely when rotated by hand g To check adjustment grasp the locknut 24A and lockcollar 24B with fingers and rota...

Страница 12: ...damaged 7 Vibration from improperly anchored piping 8 Bent shaft or drive coupling misaligned 9 Excessively worn rotor 10 Malfunctioning valve in the system 11 Relief valve setting too low 12 Liner in...

Отзывы: