CHAPTER 6: Control the power outlets
The syntax of the command line is:
Pxy=z
Parameter
Value
Function
x
1 to 5
represents the number of the Power Switch:
1 means Power Switch Master Twin
2 to 5 means the corresponding connected Satellite
y
0
1 to 8
means that all the sockets have to be controlled together
indicates the number of the socket you want to control
z
0
Command to switch the socket(s) Off
1
Command to switch the socket(s) On
r
Command to restart the socket(s)
t
Command to toggle the state of the socket
Example to control the Master:
P10=1 <ENTER> switch all the 8 sockets ON
P10=0 <ENTER> switch all the 8 sockets OFF
P14=r <ENTER> restart socket 4
P18=t
<ENTER> toggle socket 8
Example to control the first Satellite connected to the Master
DIP-Switch of the Satellite: 1 = off and 2 = off
P20=1 <ENTER> switch all the 8 sockets ON
P25=0 <ENTER> switch socket 5 OFF
Remarks:
-
The Power Switch accepts lower case and upper case commands.
-
The Power Switch sends an echo for each received character.
-
If the Twin mode is activated, sending a command to a specific socket number will also control its
corresponding twin socket.