BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
82
Click on Inputs tab.
Click Add.
In the pop up window:
Click on + in Input field
In the next opened window, select the IN2 line of the reader,
which is mounted next to the cold/hot aisle containment sliding
door. In AR122 readers, this line is also used to control the
reader's tamper.
To add IN2 line:
Drop down Object->Name list and select input IN2 of the
reader, which controls aisle door.
The program will propose a name for the selected object
Confirm the suggestion by clicking Yes.