BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
45
7.2
Card reader low level configuration
Connecting the reader
For low-level configuration, the reader should be connected to the computer via the RUD-1 interface. If the reader is already installed on
the cabinet door, then:
1.
Disconnect the reader's AW111 cable from the controller by unplugging the RJ45 connector.
2.
Connect the RJ45 plug of the AW111 cable to the RUD-1 interface as shown in the figure below.
Putting the reader into the service mode
AR121 and AR122 readers (UNIQUE readers) do not require any
additional steps.
In AR131 and AR132 readers (Mifare readers) you should:
1.
Remove the MEM jumper on the reader
2.
Restart the reader (turn off and turn on the power or short
RST jumper for a moment) - orange LED SYSTEM reader will
start to flash
3.
The reader is ready for low-level configuration
After completing the configuration, put the MEM jumper back,
which will enable later remote configuration of the reader from
the VISO program.