2.10  Operation tests and nomaly diagnosis 

2.8 

EN

INSTALLATION

The key lock is activated by keeping the Timer 

 symbol 

on the touch-screen display pressed for  t h r e e 
seconds.  Any action is prevented by the user. 

The stand-by symbol flashes at 1 second intervals.
To deactivate the lock, keep the Timer symbol pressed for 
three seconds once again.
Any key on the remote control deactivates the lock!

The lock remains active also for the next operations performed 
via remote control and in the event of a power failure.

Brightness regulation

The display brightness sensor can be disabled (still leaving 
the maximum brightness) by holding the nocturnal well-
being button (moon symbol) for 10 seconds. The display 
will show "ds" (disabled) or "En" (enabled).

Key Lock touch screen display and brightness adjustment

Display code

Cause

E1

Broken room temperature RT probe 

E2

Broken evaporative battery IPT probe

E3

Broken outdoor air temperature OT probe

E4

Broken conditioner battery OPT probe

E5

Broken indoor air fan motor

E6

Broken outdoor air fan 

E7

Lack of communication with the display

E8

Compressor discharge probe failure (only for DC Inverter models) 

The conditioner can perform a short self-diagnosis cycle 
to check the temperatures detected by the 4 probes and 
the status of the 3 inlets. 
In order to activate the self-diagnosis function, press the 

 button within 10 seconds from the electric power 

supply.
The display will lit all symbols for 2 seconds and then it will 
show the 7 information at 2 second intervals.

After 5 cycles, or when any key is pressed either in the 
display or on the remote, the self-diagnosis mode will 
stop.

If the conditioner blocks because of an alarm (see following 
table), please communicate to the assistance centre the 
code on the display to facilitate interventions.

2.11  Hotel function

Hold the air exchange button (arrows symbol) for 10 
seconds and enable the function ("

En

" displayed) to 

deactivate the dehumidification and Auto functions 
(therefore only ventilation, heating and cooling are on). The 

settings are "limited" to range from 22 to 28 for cooling 
and from 16 to 24 for heating.

Should any anomaly occur in the condensation water 
system, the maximum level float blocks the conditioner 
and the 

OF

 code appears on the display. 

During cooling and dehumidification, electronics switches 
the compressor off and keeps the water distribution 
system active with the battery - together with the fan - to 
disperse excess water in the container.  If the problem 

persists, please contact the assistance service.
During heating, condensations should drain freely through 
the specific pipe. In the event of an alarm, check that 
the condensation pipe is not bent or obstructed, thus 
preventing the water from flowing out.

Emergency condensation air discharge

If the presence contact is not closed, the appliance 
doesn't start and the 

CP

 alarm appears on the display.

Open CP contact  

It is possible to deactivate the heating or the cooling 
modes following a simple procedure.
Keep the A key on the touch-screen display pressed for 
5 seconds until 

HC

 (heating and cooling) appears on the 

display.
Press the A key for 1 second for the 

Co

 (cooling only) 

mode.
Press the A key again for Ho (heating only) mode.
Wait for 3 seconds without touching anything to memorise 
the setting.

Setting cool only or heat only modes

Содержание BKL line FX i10

Страница 1: ...GB INSTALLATION AND USE MANUAL AIR CONDITIONERS Flash FX i10 i11 Inverter Without Outdoor Unit COOLING ...

Страница 2: ......

Страница 3: ...ronment and health and encourages the recycling of product materials For further detailed information regarding available collection systems please contact your local waste disposal service or the shop where you made your purchase Disposal rules for the old air conditioner Before disposing of your old air conditioner make sure that it is off and unplug it The refrigerant it contains requires a spe...

Страница 4: ...ion 45 2 7 High low installation configuration 46 2 8 Setting cool only or heat only modes 47 2 9 Key Lock touch screen display and brightness adjustment 47 2 10 Operations tests and anomaly diagnosis 47 2 11 Hotel function 47 2 12 Heating operation only for FLASH FX i11 model 48 2 13 Wiring diagram 50 Maintenace 3 1 Periodic Maintenance 52 3 2 Troubleshooting 53 3 3 Technical specifications 54 Us...

Страница 5: ... Do not modify or tamper with the appliance as this could lead to dangerous situations and the manufacturer will not be liable for any damage caused Attention Cutting danger please wear suitable gloves If conditions occur please respect the rules for works at height Refrigerant must always be recovered and never be disposed directly into the environment Refrigerant must never be released into the ...

Страница 6: ...ing materials as they could be a source of danger It is forbidden to climb onto the appliance and or to place any type of object on top of it Exposure controls personal protection Control parameters AEL 8 h TWA 1000 ml m for each of the two components Respiratory protection For gas recovery and maintenance work in tanks use an independent breathing apparatus The vapour is heavier than air and can ...

Страница 7: ... outlet air They open when the unit is working and close when it s turned off Better indoor comfort less dust noise and pollution less maintenance and even less outdoor visibility Remote control and touch screen display In addition to the remote control the touch screen display on the unit enables the setting of any function There s even a lock mode to avoid any improper use It is possible to deac...

Страница 8: ...control Paper template for holes CR2025 3V remote control battery Wall inlet pipes 2 pcs Energy efficiency label Bottom cover acc provided separately Screws for mounting the bottom cover 2 pcs acc provided separately Installation manual Counter flange for internal wall C D A A I F E B O G A H L M N GENERAL Shipping dimensions and weight Packaging Dimensions Gross Weight Supplied components The sup...

Страница 9: ...se order 1 2 3 1 2 3 6 6 7 3 4 5 8 12 2 10 9 11 11 1 13 3 4 5 14 2 17 1 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Air outlet flaps Touch screen display Front panel Outdoor air suction Outdoor air outlet Air suction grid Air filters Condensate drain pipe Sonda aria ambiente Terminal block power supply Aesthetic side panel Anti lifting bracket External air supply fan Outdoor air heat exchanger...

Страница 10: ...d in the picture The wall on which you wish to anchor the unit must be robust and able to support its weight Leave enough space around the unit to perform maintenance operations Nothing must obstruct the air flow both in the top suction part curtains plants furniture and in the lower outlet part as it could cause vibrations which might prevent the appliance from working correctly The appliance mus...

Страница 11: ...careful that it doesn t hit people or objects In order to avoid breaking the outer plaster be careful while drilling the final part of the hole and ease the pressure on the core drill Drill the 6 holes for the bracket as indicated on the template The appliance weights more on the right so make sure to secure it properly on this side The holes must have an 8 mm diameter to accommodate the 6 supplie...

Страница 12: ...is necessary to perform a siphoning operation before inserting the pipe in the main drainage Said siphon must be placed at least 300 mm under the mouth of the appliance If the line flows into a container e g a tank do not close the container hermetically and avoid immersing the draining pipe into the water The hole for the condensation pipe must always lean towards the outside The exact position i...

Страница 13: ......

Страница 14: ...he condensation drain must be carried out after having spaced the appliance from the wall using a wooden wedge or any other similar object Once the work is done check that there are no openings on the back of the appliance especially where the air ducts are connected A B C C PARETE LATO INTERNO INSIDE WALL PARETE LATO ESTERNO OUTSIDE WALL A B C Junction line Hook Flap in vertical position Once ins...

Страница 15: ...ed in the installation template recommended for installations in the upper part of the wall Please check that the power supply is provided with suitable protections against overloads and or short circuits using a 10 at delay fuse or other equivalent devices is recommended This operation must be performed only by the installer or by authorised personnel in compliance with current national regulatio...

Страница 16: ...ght of the air outlet mouth and place it in the lower hole Remove the upper grill Remove the two plastic side panels by moving them up Unscrew the fixing screws Remove the front panel Place the bottom cover and fix it with the supplied screws Refit in the reverse order After adjusting the air outlet flap position it is necessary to set up the electronic control of the appliance Keep pressed the bu...

Страница 17: ...pressed either in the display or on the remote the self diagnosis mode will stop If the conditioner blocks because of an alarm see following table please communicate to the assistance centre the code on the display to facilitate interventions 2 11 Hotel function Hold the air exchange button arrows symbol for 10 seconds and enable the function En displayed to deactivate the dehumidification and Aut...

Страница 18: ... temperature increases abnormally the compressor operating frequency increases abnormally Heating operation only for FLASH FX i11 model The compressor will not restart before a certain time has passed about three minutes from the previous stop It is not possible to stop and restart the compressor without waiting at least three minutes This is provided for in the operating logic of the unit so as t...

Страница 19: ... the conditioner this would damage the appliance Do not move the horizontal air outlet flap manually Always use the remote control to carry out this operation In the case of water leaks from the appliance turn it off and switch off the power supply immediately Then call the closest assistance centre During heating operation the conditioner periodically removes ice that may have formed on the exter...

Страница 20: ...50 S I U 2 13 Wiring Diagram GIALLO VERDE BLU MARRON Only for model 1118 DC Solo per il modello 1118 DC Seulement pour le modèle 1118 DC Solo para modelo 1118 DC INSTALLATION ...

Страница 21: ... at 25 C Ambient temperature sensor located under the grid asp NTC 5 28kΩ at 25 C Compressor discharge temperature probe NTC 58kΩ at 25 C Reversing valve esVinv Valve exhaust water basin 230VAC 5A CN6 Outfan_power Water Pump balleria inf turn it in summer 230VAC 5A 230VAC for lower fan Supply for indoor fan DC Pilot signal 0 10V external fan Driving stepper motor air outlet diffuser Free touch scr...

Страница 22: ...a period of inactivity The filter is placed on the top part of the appliance NB before performing any operation take care with the hot and or sharp surfaces of the metal The filter is located in the top part of the appliance To extract the filters open the grille and carry out operations 1 2 3 then remove it from its housing extract the filters by lifting them remove the dust from the filter with ...

Страница 23: ...the thermal refrigeration load of the room with the following advice Cover large windows exposed to sunlight with curtains or with external maskings blinds porches reflecting films etc The room must remain closed for as long as possible Avoid turning on halogen lamps or other high energy consumption appliances such as small ovens steam irons cooking plates etc Alarm displayed Cause Functioning E1 ...

Страница 24: ...ply voltage V ph Hz V ph Hz 230 1 50 230 1 50 Additional electrical resistance kW 1 00 Maximum power input kW 1 06 2 06 Maximum current A 4 8 9 1 Diameter outdoor connection holes Ø mm 162 162 Wheelbase outdoor connection holes mm 293 293 Indoor air flow m3 h 270 400 270 400 Outdoor air flow m3 h 340 480 340 480 Sound power level dB A 58 58 Refrigerant load R410A GWP 2088 CO2eq kg t 0 56 1 17 0 56...

Страница 25: ...n the upper part of the appliance especially if it contains liquids It could cause a short circuit damage the appliance and or be exposed to an electric shock hazard Do not lean or sit on the air conditioner to avoid serious damage to its external parts Do not move the horizontal air outlet flap manually Always use the remote control to perform such operation In the event of water leaks turn off t...

Страница 26: ...atteries open the specific cover in the bottom part of the remote The battery must be inserted respecting polarity Once the battery is inserted close the cover In order to manage the appliance using the remote control and the touch screen the main switch on the electrical power supply line must be turned on its exact position can be indicated by the technician who installed the appliance or the po...

Страница 27: ...d the appliance does not intervene on room temperature or humidity IT is possible to choose the fan speed Heating only mode In this mode the appliance heats the room Set on heating only mode the appliance defrosts the evaporative battery periodically if necessary During this phase the conditioner does not dispense warm air even if its internal organs are on except for air ventilation It is possibl...

Страница 28: ...y Operating aspects that must not be interpreted as problems Managing the appliance if the remote control is not available Key Display Operation Fan speed control By pressing this button the speed changes according to the following sequence Minimum Medium Maximum and Automatic The higher the speed the better the performance though the appliance will be more noisy By selecting the Automatic speed w...

Страница 29: ...r try to interfere with the refrigerant circuit yourself or disassemble the product yourself and always ask a professional EER rated 3 2 Cooling energy efficency class A Indicative hourly electricity consumption in cooling QDD 0 7 kWh 60min Energy consumption 0 7 kWh per 60 minutes based on standard test results Actual energy consumption will depend on how the appliance is used and where it is loc...

Страница 30: ... with the refrigerant circuit yourself or disassemble the product yourself and always ask a professional EER rated 3 2 Cooling energy efficency class A Indicative hourly electricity consumption in cooling QDD 0 7 kWh 60min Energy consumption 0 7 kWh per 60 minutes based on standard test results Actual energy consumption will depend on how the appliance is used and where it is located Cooling capac...

Страница 31: ... kept Please print in block letters Model S N indoor unit S N indoor unit S N indoor unit S N outdoor unit Date installation first running User Street y r t n u o C n w o T p i Z Installer Street y r t n u o C n w o T p i Z After sale service Street y r t n u o C n w o T p i Z Slip B for distributor Please print in block letters Model S N indoor unit S N indoor unit S N indoor unit S N outdoor uni...

Страница 32: ...rodotti in qualunque momento esenza preavviso tutte le modifiche ritenute opportune per qualsiasi esigenza di carattere tecnico o commerciale The manufacturer denies all responsibility for any errors or inaccuracies in this manual andreserves the right at any time and without notice to make any modifications to its products if judged necessary to meet any technical or commercial need ...

Отзывы: