Programmable DC Power Supplies
Models 1696B, 1697B & 1698B
3
www.bkprecision.com
v091819
Specifications
Note: All specifications apply to the unit after a temperature stabilization time of 30 minutes over an ambient temperature range of 23 °C ± 5 °C.
Model
1696B
1697B
1698B
Output Rating
Voltage
1 to 20 V
1 to 40 V
1 to 60 V
Current
0 to 10 A
0 to 5 A
0 to 3.3 A
Max Output Power
200 W
Load Regulation
Voltage
≤
200 mV
≤
200 mV
≤
100 mV
Current
≤
25 mA
≤
15 mA
≤
10 mA
Line Regulation
Voltage
≤
10 mV
Programming/Readback Resolution
Voltage
10 mV
Current
1 mA
Power
1 mW
Meter Accuracy
Voltage Meter
± (1% + 2 counts for V > 5 V)
Current Meter
± (1% + 2 counts for I > 0.5 A)
Ripple & Noise
Voltage
≤
30 mVp-p /
≤
6 mVrms
Current
≤
10 mArms
General
Efficiency
≥
70%
AC Input
100 to 240 VAC ±10%, 50/60 Hz
Display Meter
4-digit voltage, current and power meter
I/O Interface
USB (type B), RS485
Operating Temperature
32 °F to 104 °F (0 °C to 40 °C),
≤
80% R.H
Safety
LVD: EN61010-1:2010
Electromagnetic Compatibility
EN55011, EN61000-3-2, EN61000-3-3, EN61000-6-1
Dimensions
7.6” x 3.85” x 8.46” (193 mm x 98 mm x 215 mm)
Weight
6.6 lbs. (3 kg)
Warranty
2 years
Included Accessories
PC software, RS485 adapter, USB cable, and test report
Optional Accessories
RS232 to RS485 adapter (ATR-2485)
Содержание 1696B Series
Страница 1: ......
Страница 21: ...PC Software Control and Installation 21 Figure 7 13 Figure 7 14 Figure 7 15...
Страница 22: ...PC Software Control and Installation 22 Figure 7 16 Figure 7 17 SCPI Selection Figure 7 18...
Страница 23: ...PC Software Control and Installation 23 Figure 7 19 Figure 7 20 Figure 7 21...
Страница 24: ...PC Software Control and Installation 24 Figure 7 22 Figure 7 23 Figure 7 24 Figure 7 25...