Modbus Interface manual
LMC341 DIWE
Page 17
9. Trouble shooting
• Check if there is power to the LMC341 DIWE,
range 15 - 30 VDC/12 – 24 VAC.
• Check if Data+ and Data- wires have been switched.
• Check if the communication node
adress setting matches the selected.
Note: Node address should be between 1 and 247, both
included.
• Check if the communication speed matches the selected.
• Check if communication is running.
The LUP200 display will show readings and commands.