
33
4.4
ANGLED WALL RADIATION SHIELD
(XRSMI30, XRSMI45, AC10RSMI30)
When traversing a combustible wall with the chimney at a 30º or 45º angle, an angled
firestop or wall radiation shield must be installed. Only one is required.
Note: 45º angle for Canada only
In cold climate locations, we recommend that you use the insulated wall radiation shield
since it will maintain the home’s thermal barrier.
XRSMI30, XRSMI45,AC10RSMI30
CHIMNEY (7" dia.)
ANGLE
HOLE DIMENSION
Secure Temp
S2100+
Nova Temp
Secure Temp
GX
(US only)
30º
15" x 38 _" (380 mm x 972 mm)
Secure Temp
S2100+
Nova Temp
45º
Canada only
15" x 25 7/8" (380 mm x 657 mm)
ACBI
30º
17" x 42 _" (432 mm x 1080 mm)
Tableau 5
Figure 35
Содержание TRADITION
Страница 2: ...Printed in Canada Rev 5 April 2007 PIBISTRAD ...
Страница 8: ...3 2 CERTIFICATION LABEL ...
Страница 16: ...11 Make sure that the blower is at the off position when you open the fireplace door for reloading ...
Страница 23: ...18 INSULATED CHASE CONSTRUCTION Figure 12 ...
Страница 37: ...32 Figure 34 Figure 33 ...